11.12.2012 Views

Master Control - Berker

Master Control - Berker

Master Control - Berker

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

4.2.4.12.5 Fault<br />

Cause of fault and fault behaviour<br />

The signalling system switches to the "Fault" status when the sabotage detector has tripped in<br />

unarmed or if, during detector monitoring while unarmed, at least one missing detector was detected.<br />

If the system is armed, then these events will lead to an immediate alarm. In this case,<br />

the system will switch to the "Fault" status, when the alarm has been acknowledged.<br />

A fault restricts the function of the signalling system to such an extent that proper operation can<br />

no longer be guaranteed. A fault causes the system to no longer be armed for as long as the<br />

fault has not been eliminated. The detector list and the event memory can be used to detect the<br />

cause of the fault and the time the fault was activated.<br />

If there is a system fault, the panel transmits a "1" telegram via the "Fault" object. This allows<br />

any switching function to be executed in the bus along with other signalling operations, e.g. using<br />

a transmission device. An -email, predefined in the panel, can be set by linking this object<br />

with an e-mail event (see chapter 4.2.4.13.1. Introduction).<br />

If the fault was triggered by a missing detector, the signalling system uses the<br />

14 byte object "Fault detector text" to display the detector text of the faulty detector. If several<br />

detectors are missing, then the detector text of the detector is transmitted which was most recently<br />

detected as missing.<br />

If the fault was triggered by the sabotage detector, then the test "Sabotage" is transmitted to the<br />

bus via the 14 byte object.<br />

The fault status continues to remain active, even if the cause of the fault has already been eliminated.<br />

The status is only reset after the system operator has acknowledged the fault directly on<br />

the panel.<br />

Acknowledgement of a fault message<br />

A fault must always be acknowledged directly on the panel. Without a fault acknowledgement, it<br />

is not possible to switch back to "Unarmed" status and thus additional arming. The cause of the<br />

fault must have been eliminated in order to be able to acknowledge a fault. This means that the<br />

sabotage detector may ot be active before acknowledgement, ad all the detectors of the security<br />

areas must have been detected as existing. The detector list can be used to detect which detectors<br />

may be preventing the acknowledgement of a fault.<br />

After the operator has acknowledged a fault, the panel uses the "Fault" object to transmit a<br />

"0" telegram and, via the 14 byte object "Fault detector text", the text "No fault" to the bus. After<br />

this, the signalling is system is ready for operation again.<br />

i After an alarm has been acknowledged, the system automatically switches to the "Fault"<br />

status, if, for example, the sabotage input was the detector triggering the alarm. This subsequent<br />

fault must then be acknowledged separately on the panel in the manner described.<br />

Order-No. 7574 00 1X<br />

Software "...590101"<br />

Functional description<br />

Page 124 of 222

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!