4.2.4.1.4 Download behaviour<br />
After commissioning, the operator can make various settings directly on the panel while the system<br />
is running. These include the names and settings of light scenes, switching times and limit<br />
values.<br />
During first commissioning of a device with new project planning data, these parts must be overwritten.<br />
For this, set the parameters "Overwrite light scene names, delete values", "Overwrite all<br />
timer switch switching times" and "Overwrite limit values" to "Yes". These parameters are located<br />
in the "Download behaviour" parameter group of the ETS plug-in.<br />
After first download, the parameters can be reset to "No" to maintain any changes made by the<br />
user in subsequent programming operations.<br />
Exceptions: with later project planning changes, the parameters must be set to "Yes" after<br />
changes, so that the changes are transferred correctly to the device memory of the panel.<br />
- Light scenes added or deleted<br />
- Light scene groups added or deleted<br />
- Sequence of light scenes changed<br />
- Type of light scene groups (communication objects) changed<br />
- Timer switch channels added or deleted<br />
- Sequence of timer switch channels changed<br />
- Function of the timer switch channels (type of communication objects) changed<br />
- Value display (EIS type, data point type) of a monitored value changed<br />
- Value monitoring activated or deactivated<br />
- Top or bottom limit value activated or deactivated<br />
- Numeric value of a limit value changed.<br />
i The parameter "Overwrite all switching times of the timer switch" should be set to "Yes", if<br />
the switching times predefined in the ETS plug in should be reloaded into the panel after<br />
each programming operation.<br />
Order-No. 7574 00 1X<br />
Software "...590101"<br />
Functional description<br />
Page 45 of 222