Function: Signalling system<br />

Object<br />

h<br />

Function<br />

Signalling system output<br />

Order-No. 7574 00 1X<br />

Name<br />

Unarming acknowledgement<br />

Type<br />

1 bit<br />

DP type<br />

1,001<br />

Description 1 bit object to signal that the signalling system was unarmed internally or externally.<br />

The object is dynamic, meaning that it is only "1" for the unarming acknowledgment<br />

period specified in the ETS. In the armed state or if the unarming<br />

acknowledgment time has elapsed, the object value is "0".<br />

For example, appropriate pulse blocking elements can be connected to this<br />

signal output.<br />

Function: Signalling system<br />

Object<br />

h<br />

Function<br />

Signalling system output<br />

Name<br />

Fault<br />

Type<br />

1 bit<br />

DP type<br />

1,001<br />

Description 1 bit object for signalling a fault within the signalling system (missing detector,<br />

active sabotage input).<br />

0 = No fault / 1 = Fault.<br />

Function: Signalling system<br />

Object<br />

h<br />

Function<br />

Signalling system output<br />

Name<br />

Alarm detector text<br />

Type<br />

14 byte<br />

DP type<br />

16,001<br />

Description 14 byte object to transfer a 14 character detector text to the bus. If there is an<br />

alarm, the signalling system sends the signal text of the detector triggering the<br />

alarm to the bus via this object. The detector text can be configured separately<br />

for each detector in the ETS.<br />

Function: Signalling system<br />

Object<br />

h<br />

Function<br />

Signalling system output<br />

Name<br />

Fault detector text<br />

Type<br />

14 byte<br />

DP type<br />

16,001<br />

Description 14 byte object to transfer a 14 character detector text to the bus. If there is an<br />

alarm, the signalling system sends the signal text of the detector which caused<br />

the fault (missing detector) to the bus via this object. The detector text can be<br />

configured separately for each detector in the ETS.<br />

Function: Signalling system<br />

Object<br />

h<br />

Function<br />

Signalling system output<br />

Name<br />

Prealarm signalling,<br />

internal<br />

Type<br />

1 bit<br />

Software "...590101"<br />

DP type<br />

1,001<br />

Object table<br />

Description 1 bit object to signal an elapsing prealarm with internal arming. In the case of<br />

previously detected break-in of sabotage alarm, this signal output is "1" for the<br />

length of the alarm delay time configured in the ETS. Otherwise the object<br />

value is "0".<br />

Flag<br />

C, T<br />

Flag<br />

C, T<br />

Flag<br />

C, T<br />

Flag<br />

C, T<br />

Flag<br />

C, T<br />