i Ensure that a unique group address is used in the ETS project for the collective feedback<br />

of an actuator. This group address must be connected with the collective feedback object<br />

of the actuator and with the collective feedback objects of various display elements of the<br />

panel (max. 16). Ensure that, at no time, more than one actuator is connected with a collective<br />

feedback group address. If the collective feedback of various actuators is to be displayed<br />

on the panel, then multiple group address must be used.<br />

Dimmer actuator load type:<br />

Some KNX/EIB dimmer actuators permit feedback of the load type set or measured at the load<br />

output to the bus. In this way, one can identify the dimming principle according to which the dimmer<br />

output is working. With universal dimmer actuators, it is thus possible to determine whether<br />

the dimmer output has adjusted to forward phase or inverse phase operation.<br />

Feedback of the load type is provided using a 1 byte object in each dimmer actuator channel.<br />

The object must possess the value encoding shown in Table 2.<br />

Object value Meaning<br />

0 Load type undefined<br />

1 Load type capacitive / ohmic<br />

2 Load type, inductive<br />

3 Load type, universal, dimmer actuator adjusted to capacitive or ohmic load<br />

4 Load type, universal, dimmer actuator adjusted to inductive load<br />

5...255 Not used<br />

Table 2: meaning of the object values for a dimmer actuator load type<br />

The panel is able to display the feedback of a load type in a display element. In this case various<br />

image texts or status icons can be configured in the parameter group of the appropriate display<br />

element according to the load type meanings shown in Table 2. When the panel receives a<br />

telegram value to which no load type meaning is assigned (values 5...255), then the panel will<br />

only show dashes in the display element.<br />

Operating function<br />

Each display element can also be configured for an operating function in addition to the display<br />

function. Four function buttons can be shown at the bottom edge of the panel for each display<br />

element and can be operated by touching them (see picture 15). The operating function of a display<br />

element is only available when the parameter "Element selectable" is set to "Yes".<br />

Order-No. 7574 00 1X<br />

picture 15: Function buttons of a display element<br />

Software "...590101"<br />

Functional description<br />

Page 60 of 222