- "Arming acknowledgement":<br />

This object dynamically signals successful internal or external arming for the length of the<br />

"Arming acknowledgement time" set in the ETS plug-in. No distinction is made between the<br />

security areas. The object value switches to "1" as soon as the system has armed. The object<br />

value returns to "0" automatically when the arming acknowledgement has elapsed. It is<br />

possible to cancel arming acknowledgement by unarming before the arming acknowledgement<br />

time has elapsed.<br />

- "Unarming acknowledgement":<br />

This object dynamically signals successful internal or external unarming for the length of<br />

the "Unarming acknowledgement time" set in the ETS plug-in. No distinction is made<br />

between the security areas. The object value becomes "1" as soon as the system has unarmed<br />

(status change "Armed -> Unarmed" or "Alarm -> Unarmed after alarm"). When the<br />

status changes from "Unarmed after alarm -> Unarmed", there is no unarming acknowledgement.<br />

The object value returns to "0" automatically when the unarming acknowledgement<br />

has elapsed. It is possible to cancel unarming acknowledgement by arming before<br />

the unarming acknowledgement time has elapsed.<br />

i If, after an arming command (or after an arming delay has elapsed), the signalling system<br />

does not arm, because the affected security areas are not ready to arm, there will be no acknowledgement.<br />

In this case, the dynamic object "Arming acknowledgement" and, in the<br />

case of external arming, the visual signal encoder are not controlled (no negative acknowledgement).<br />

i To be able to distinguish between dynamic objects for arming and unarming, the acknowledgement<br />

times for "Arming" and "Unarming" should be of different lengths. When arming<br />

or unarming is repeated ("Armed" -> "Armed", "Unarmed" -> "Unarmed"), there is no retriggering<br />

of the dynamic signalling. This is only transmitted once on changing status.<br />