h Signalling system -> General<br />

Arming acknowledgement<br />

time [s]<br />

Unarming acknowledgement<br />

time [s]<br />

Switching time, internal<br />

siren [s]<br />

Order-No. 7574 00 1X<br />

Software "...590101"<br />

Parameters<br />

cipient address must be entered for<br />

each event e-mail.<br />

2...3...255 This parameter specifies the acknowledgement<br />

time for system arming. Acknowledgement<br />

takes place using the<br />

"Arming acknowledgement" object and,<br />

in the case of external arming, additionally<br />

using the visual alarm (depending<br />

on the parameter "Optical acknowledgement<br />

for external arming").<br />

It is possible to cancel arming acknowledgement<br />

by unarming before the arming<br />

acknowledgement time has elapsed.<br />

2...3...255 This parameter specifies the acknowledgement<br />

time for system unarming.<br />

Acknowledgement takes place using the<br />

"Unarming acknowledgement" object.<br />

It is possible to cancel arming acknowledgement<br />

by unarming before the arming<br />

acknowledgement time has elapsed.<br />

2...90...255 If a detector within an armed area responds,<br />

or a sabotage detector triggers<br />

when armed or any detector is found to<br />

be missing, the signalling system<br />

switches to the "Alarm" status and activates<br />

the internal siren. The internal siren<br />

is an alarm encoder activated for a set<br />

period of time. The system project planner<br />

must set the switching length of the<br />

internal siren here.<br />

The signalling system automatically deactivates<br />

the internal siren when the<br />

switching time after the alarm is<br />

triggered has elapsed.<br />

Detector poll interval [s] 10...255 The signalling system checks that the<br />

detectors created in the security areas<br />

exist, i.e. that they are still connected to<br />

the KNX/EIB and are functioning. The<br />

"Detector poll interval", which can be set<br />

in this parameter, defines the time<br />

between two read telegrams of the panel,<br />

i.e. the time between two detector<br />

tests. The signalling system polls all the<br />

created detector inputs in turn in this<br />

way.<br />

Example: poll interval: 10 s, 40 detectors<br />

have been created. -> A detector is<br />

polled every 10 s. After approx. 400 s,<br />

all the detectors have been tested. After<br />

this, the cycle test is continued again<br />

with the first detector.<br />

The signalling system tests detectors<br />

Page 198 of 222