Function: Signalling system<br />

Object<br />

h<br />

Function<br />

Signalling system input<br />

Order-No. 7574 00 1X<br />

Name<br />

Sabotage<br />

Type<br />

1 bit<br />

DP type<br />

1,001<br />

Description 1 bit object as a sabotage of the signalling system. The sabotage detector can<br />

be connected to this object.<br />

0 = No sabotage, detector inactive / 1 = Sabotage, detector active<br />

Function: Signalling system<br />

Object<br />

h<br />

Function<br />

Signalling system output<br />

Name<br />

Ready to arm, internal<br />

Type<br />

1 bit<br />

DP type<br />

1,001<br />

Description 1 bit object to signal that the signalling system is internally ready to arm. The<br />

system is only internally ready to arm when none of the detectors allocated to<br />

the external skin is active and there is no fault.<br />

0 = Not ready to arm / 1 = Ready to arm<br />

Function: Signalling system<br />

Object<br />

h<br />

Function<br />

Signalling system output<br />

Name<br />

Ready to arm, external<br />

Type<br />

1 bit<br />

DP type<br />

1,001<br />

Description 1 bit object to signal that the signalling system is externally ready to arm. The<br />

system is only externally ready to arm when none of the detectors allocated to<br />

the internal skin and the external skin is active and there is no fault.<br />

0 = Not ready for arming / 1 = Ready for arming<br />

Function: Signalling system<br />

Object<br />

h<br />

Function<br />

Signalling system output<br />

Name<br />

Alarm<br />

Description 1 bit object to signal a break-in or sabotage alarm.<br />

0 = No alarm / 1 = Alarm<br />

Function: Signalling system<br />

Object<br />

h<br />

Function<br />

Signalling system output<br />

Name<br />

Arming message,<br />

internal<br />

Type<br />

1 bit<br />

Type<br />

1 bit<br />

Software "...590101"<br />

DP type<br />

1,001<br />

DP type<br />

1,001<br />

Object table<br />

Description 1 bit object for static signalling that the signalling system has successfully<br />

armed internally, i.e. the external skin monitoring is active.<br />

0 = External skin monitoring not armed / 1 = External skin monitoring armed<br />

Flag<br />

C, S<br />

Flag<br />

C, T<br />

Flag<br />

C, T<br />

Flag<br />

C, T<br />

Flag<br />

C, T<br />