Internal arming via the<br />

signal page<br />

External arming via the<br />

signal page<br />

Order-No. 7574 00 1X<br />

Yes<br />

No<br />

Yes<br />

No<br />

h Signalling system -> Internal arming<br />

Arming delay, internal<br />

[s]<br />

Alarm delay time, internal<br />

[s]<br />

Software "...590101"<br />

Parameters<br />

considered missing cyclically at brief intervals,<br />

in order to be able to detect<br />

quickly whether or not the detector has<br />

reconnected.<br />

The system can be internally armed or<br />

unarmed using the a display element on<br />

the "Signalling system" screen page.<br />

This parameter can be used to hide the<br />

display element for internal arming ("No"<br />

setting), so that the system can only be<br />

internally armed or unarmed using the<br />

appropriate communication object.<br />

The system can be externally armed or<br />

unarmed using the a display element on<br />

the "Signalling system" screen page.<br />

This parameter can be used to hide the<br />

display element for external arming<br />

("No" setting), so that the system can<br />

only be externally armed or unarmed using<br />

the appropriate communication object.<br />

0...255 The arming delay time, which can be set<br />

here, specifies after what time after a<br />

arming command ("1" telegram via the<br />

"Internally armed" object or pressing of<br />

the "Arm" button on the panel) the system<br />

is actually internally armed. In so<br />

doing the signalling system only checks<br />

the arming readiness of the security<br />

areas after the delay time has elapsed.<br />

Should a detector still be active at the<br />

end of the arming delay, (e.g. window<br />

opened), then arming does not take<br />

place.<br />

An elapsing arming delay can be cancelled<br />

at any time by unarming.<br />

The setting "0 s" deactivates the arming<br />

delay for the internal arming operation.<br />

When setting the time, a time reserve<br />

should be planned, so that the user is<br />

still able to leave the building area to be<br />

secured correctly before actual arming.<br />

0...255 An alarm delay can optionally be configured<br />

for the internal alarm. An alarm<br />

delay is often used when the switching<br />

device (e.g. the panel or a button<br />

sensor) is installed in the secure area. In<br />

such cases, authorised people must be<br />

able to enter the secured building area,<br />

meaning the status the switching device<br />

for unarming can only be reached after a<br />

delay.<br />

Page 199 of 222