Difference formation Yes<br />

No<br />

Start value for difference<br />

formation<br />

Poll object cyclically Yes<br />

No<br />

Order-No. 7574 00 1X<br />

Month (31 intervals<br />

of 1 day)<br />

Year 1 (12 intervals<br />

of 1 month)<br />

Year 2 (52 intervals<br />

of 1 week)<br />

Software "...590101"<br />

Parameters<br />

and maximum interval value determined.<br />

In addition, an average value is calculated<br />

and saved.<br />

If the data source is a counter<br />

(e.g. electricity meter, people counter,<br />

etc.), data recording can be switched to<br />

differential calculation here. In so doing,<br />

a differential between the last received<br />

value and the last value of the previous<br />

period is calculated and stored as a display<br />

data value in the panel. No calculation<br />

of minimum, maximum or average<br />

values take place. The calculated data<br />

value differentials then, in the case of an<br />

electricity meter, directly represent the<br />

consumed units of power within a recording<br />

period (e.g. month or year).<br />

0 After a device reset (power failure, programming<br />

operation), the differential calculation<br />

starts at a specified starting<br />

value. This is required to initialise the<br />

differential formation, so that a differential<br />

value can be calculated in the first<br />

recording period after a reset. This<br />

means that, in addition, there can be an<br />

adjustment to defined basic counter<br />

levels - for example after the installation<br />

of a new electricity meter.<br />

The system project planner must enter<br />

the starting value here.<br />

A distinction must be made between two<br />

different cases:<br />

If a value is entered in the parameter<br />

box (standard value = "0"), the value<br />

then evaluates the last data value of the<br />

first time period after the reset directly<br />

and then shows the difference to the<br />

starting value in the display diagram. Alternatively,<br />

the parameter field of the<br />

start value can be left empty here. In this<br />

case, the panel automatically evaluates<br />

the first data value received as the start<br />

value.<br />

This parameter is only visible on "Differential<br />

formation = Yes".<br />

With activated cyclic polling, the panel<br />

transmits a value read telegram<br />

(ValueRead) to the bus regularly, after a<br />

period of time has elapsed. The data<br />

source must then return a value re-<br />

Page 194 of 222