The parameters of the display elements make a distinction between two possible types of operation...<br />
- Single click operation:<br />
Tapping the display element (33) automatically executes the function of function button 1.<br />
For this, it is not necessary to have the four function buttons (34) of this display element<br />
visible at the bottom edge of the screen. The parameter "Hide function keys" in the parameter<br />
group of the display element specifies whether the appropriate buttons are visible for<br />
a selected element or not. If all the function buttons are visible, then additional buttons of<br />
the element can be operated after clicking the display element and automatic execution of<br />
the function of button 1.<br />
If the scroll bar is used, in order to switch between the different display elements using the<br />
single arrows, the display elements are simply selected without direct execution of the function.<br />
- Two click operation:<br />
Tapping the display element (33) or selecting the scroll bar makes the four function buttons<br />
(34) of the display element visible without directly executing a function. Only when one of<br />
the function buttons is actuated is the stored function executed.<br />
The individual function buttons can be configured independently with the following functions.<br />
Switching:<br />
On pressing and / or releasing the button, the panel can transmit no telegram, switch on, switch<br />
off or switch.<br />
The telegram is transmitted via a separate button object.<br />
If the display element is configured for the display function "Switching", then the function buttons<br />
can be also be configured for the function "Switching function of the display element". In this<br />
case, the function button affects the communication object of the display element and not a separate<br />
object.<br />
Blind:<br />
The parameter "Blind function" determines the direction (Up, Down, Toggle) in which the drive<br />
to be controlled should travel. If the setting is "Toggle", the direction is changed after long actuation.<br />
In addition, the parameters can be adjusted to make a distinction between lamella adjustment<br />
(brief actuation) and movement (long actuation).<br />
The telegram is transmitted via two separate button objects (long-time operation and short-time<br />
operation).<br />
If the display element is configured for the display function "Blind", then the function buttons can<br />
be also be configured for the function "Blind function of the display element". In this case, the<br />
function button affects the communication objects of the display element and not separate elements.<br />
In addition, in this case, the time settings of the display element are used.<br />
Dimming:<br />
The parameter "Dimming button function" determines which switching or dimming commands<br />
the panel sends to the bus when the button is pressed for a long or short time. In addition, the<br />
parameters can be adjusted to make a distinction between switching (brief actuation) and dimming<br />
(long actuation).<br />
The telegram is transmitted via two separate button objects (switching and dimming).<br />
Alternatively, a 1 byte object with a constant brightness value can be used (parameter "Dimming<br />
button function" = "Brightness value"). In this case, the value to be transmitted on pressing the<br />
button can be configured.<br />
The telegram is then transmitted via a separate button object.<br />
If the display element is configured for the display function "Dimming", then the function buttons<br />
can be also be configured for the function "Dimming function of the display element". In this<br />
case, the function button affects the communication objects of the display element and not separate<br />
elements. In addition, in this case, the time settings of the display element are used.<br />