3-62 Programming and ParametersFileGroupNo.NameDescriptionValuesRead-WriteData Type515 MtrBrngEventActnMachine Bearing Event ActionConfigures the response to a machine bearing event, which occurs when P518[MchBrngEventLvl] is met or exceeded.Default:Options:0 = “Ignore”0 = “Ignore”1 = “Alarm”2 = “Flt Minor”3 = “FltCoastStop”4 = “Flt RampStop”5 = “Flt CL Stop”RW 32-bitInteger516 MchBrngResetLogMachine Bearing Reset LogTotal number of resets performed on the P512 [MchBrngElpsdLife] parameter.Default: 0Min/Max: 0 / 255RO32-bitIntegerPROTECTIONPredictive Main517 MchLubeElpsdHrsMachine Lubricant Elapsed HoursAccumulated machine hours since the most recent lubrication of the machinebearings. Can be reset without restriction.518 MchLube EventLvlMachine Lubricant Event LevelNumber of hours between scheduled lubrications of the machine bearings. Usedfor an early warning alarm or fault according to P519 [MchLubeEventActn]. Eventis disabled when set to 0.Units: HrsDefault: 0.00Min/Max: 0.00 / 21,474,836.47.00Units: HrsDefault: 0.000Min/Max: 0.000 / 220000000.000RO32-bitIntegerRW Real519 MchLubeEventActnMachine Lubricant Event ActionConfigures the response to a machine bearing lubrication event, which occurswhen P518 [MchLube EventLvl] is met or exceeded.Default:Options:0 = “Ignore”0 = “Ignore”1 = “Alarm”2 = “Flt Minor”3 = “FltCoastStop”4 = “Flt RampStop”5 = “Flt CL Stop”RW 32-bitIntegerDrive Speed Control FileFileGroupNo.NameDescriptionValuesRead-WriteData Type520 Max Fwd SpeedMaximum Forward SpeedSets the forward speed high limit. Refer to P524 [Overspeed Limit]. When usingan analog input for the speed reference, this parameter is scaled to P51/61 [AnlgInX Hi] on the I/O module.Units:Default:Min/Max:HzRPMP27 [Motor NP Hertz]P28 [Motor NP RPM][Motor NP Hertz] x 0.05 /[Motor NP Hertz] x 16.00[Motor NP RPM] x 0.05 /[Motor NP RPM] x 16.00RW RealSPEED CONTROLSpeed Limits521 Max Rev SpeedMaximum Reverse SpeedSets the reverse speed high limit. Refer to P524 [Overspeed Limit]. When usingan analog input for the speed reference, this parameter is scaled to P51/61 [AnlgIn X Hi] on the I/O module.522 Min Fwd SpeedMinimum Forward SpeedSets the low limit for speed reference after scaling is applied. Refer to P524[Overspeed Limit]. When using an analog input for the speed reference, thisparameter is scaled to P52/62 [Anlg InX Lo] on the I/O module.Units:Default:Min/Max:Units:Default:Min/Max:HzRPMP27 [Motor NP Hertz] x –1.00P28 [Motor NP RPM] x –1.00[Motor NP Hertz] x –16.00 / 0.00[Motor NP RPM] x –16.00 / 0.00HzRPM0.000.00 / [Motor NP Hertz] x 16.000.00 / [Motor NP RPM] x 16.00RW RealRW Real523 Min Rev SpeedMinimum Reverse SpeedSets the low limit for speed reference after scaling is applied. Refer to P524[Overspeed Limit]. When using an analog input for the speed reference, thisparameter is scaled to P52/62 [Anlg InX Lo] on the I/O module.Units:Default:Min/Max:HzRPM0.00[Motor NP Hertz] x –16.00 / 0.00[Motor NP RPM] x –16.00 / 0.00RW Real<strong>PowerFlex</strong> <strong>750</strong>-<strong>Series</strong> <strong>User</strong> <strong>Manual</strong> – Publication <strong>750</strong>-UM001C-EN-P – September 2009

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!