Programming and Parameters 3-19Drive Monitor FileFileGroupNo.NameDescriptionValuesRead-WriteData Type1 Output FrequencyOutput FrequencyOutput frequency present at terminals T1, T2, and T3 (U, V & W)Units: HzDefault: 0.00Min/Max: –/+650.00ROReal2 Commanded SpdRefCommanded Speed ReferenceValue of the active Speed/Frequency Reference. Displayed in Hz or RPM,depending on the value of P300 [Speed Units].Units:Default:Min/Max:HzRPM0.00–/+P27 [Motor NP Hertz] x 8–/+P28 [Motor NP RPM] x 8ROReal3 Mtr Vel FdbkMotor Velocity FeedbackEstimated or actual motor speed, with feedback. Displayed in Hz or RPM,depending on the value of P300 [Speed Units].Units:Default:Min/Max:HzRPM0.00–/+P27 [Motor NP Hertz] x 8–/+P28 [Motor NP RPM] x 8ROReal4 Commanded TrqCommanded TorqueFinal torque reference value after limits and filtering are applied. Percent of motorrated torque.Units: %Default: 0.00Min/Max: –/+800.00ROReal5 Torque Cur FdbkTorque Current FeedbackBased on the motor, the amount of current that is in phase with the fundamentalvoltage component.Units: AmpsDefault: Based on Drive RatingMin/Max: –/+P21 [Rated Amps] x 2ROReal6 Flux Cur FdbkFlux Current FeedbackAmount of current that is out of phase with the fundamental voltage component.Units: AmpsDefault: Based on Drive RatingMin/Max: –/+P21 [Rated Amps] x 2RORealMONITORMetering7 Output CurrentOutput CurrentThe total output current present at terminals T1, T2, and T3 (U, V & W).8 Output VoltageOutput VoltageOutput voltage present at terminals T1, T2, and T3 (U, V & W).Units: AmpsDefault: Based on Drive RatingMin/Max: 0.00 / P21 [Rated Amps] x 2Units: V<strong>AC</strong>Default: Based on Drive RatingMin/Max: 0.00 / P20 [Rated Volts] x 1.15RORORealReal9 Output PowerOutput PowerOutput power present at terminals T1, T2, and T3 (U, V & W).Units: kWDefault: 0.00Min/Max: 0.00/100.00ROReal10 Output Powr FctrOutput Power FactorOutput power factor.Default: 0.00Min/Max: 0.00/1.00ROReal11 DC Bus VoltsDirect Current Bus VoltsDC bus voltage.Units: VDCDefault: Based on Drive RatingMin/Max: 0.00 / P20 [Rated Volts] x 2ROReal12 DC Bus MemoryDirect Current Bus MemoryA six-minute average of P11 [DC Bus Volts] used to estimate the DC equivalentof the input voltage. Automatically initialized upon power-up, continually updatedduring normal operation, and is used to trigger a power loss condition.Units: VDCDefault: Based on Drive RatingMin/Max: 0.00 / P20 [Rated Volts] x 2ROReal13 Elapsed MWHElapsed Megawatt HourAccumulated output energy of the drive.Units: MWhDefault: 0.000Min/Max: 0.000 / 4294967295.000ROReal14 Elapsed kWHElapsed Kilowatt HourAccumulated output energy of the drive.Units: kWhDefault: 0.000Min/Max: 0.000 / 4294967295.000ROReal15 Elapsed Run TimeElapsed Run TimeAccumulated time drive is outputting power.Units: HrsDefault: 0.000Min/Max: 0.000 / 220000000.000ROReal<strong>PowerFlex</strong> <strong>750</strong>-<strong>Series</strong> <strong>User</strong> <strong>Manual</strong> – Publication <strong>750</strong>-UM001C-EN-P – September 2009

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!