3-158 Programming and ParametersFileGroupNo.NameDescriptionValuesRead-WriteData TypeHOST GROUPSFaults70 Config Flt CodeConfiguration Fault Code.0 = No Fault1 = Password Required (Password Req)2 = P21 [Safety Mode] value not legal based on P20 [Cascaded Config] value.3 = P57 [Door Out Type] value not legal based on P20 [Cascaded Config] value.4 = P46 [Stop Mon Delay] value not legal based on P45 [Safe Stop Type] value.5 = P50 [Decel Ref Speed] value not legal based on P31 [Fbk 1 Resolution]value.6 = P48 [Standstill Speed] value not legal based on P20 [Cascaded Config]value.7 = P53 [LimSpd Mon Delay] value not legal based on P21 [Safety Mode] value.8 = P55 [Safe Speed Limit] value not legal based on P21 [Safety Mode] and P31[Fbk 1 Resolution] value.9 = P56 [Speed Hysteresis] value not legal based on P21 [Safety Mode] value.10 = P62 [Safe Max Speed] value not legal based on P31 [Fbk 1 Resolution]value.11 = P42 [Direction Mon] value not legal based on P21 [Safety Mode] value.12 = P59 [Lock Mon Enable] value not legal based on P21 [Safety Mode] value.13 = P36 [Fbk 2 Resolution] value not legal based on P27 [Fbk Mode] value.14 = P35 [Fbk 2 Polarity] value not legal based on P27 [Fbk Mode] value.15 = P39 [Fbk Speed Ratio] value not legal based on P27 [Fbk Mode] value.16 = P41 [Fbk Pos Tol] value not legal based on P27 [Fbk Mode] value.17 = P40 [Fbk Speed Tol] value not legal based on P27 [Fbk Mode] value.18 = P44 [Safe Stop In Typ] value not legal based on P21 [Safety Mode] value.19 = P52 [Lim Spd In Typ] value not legal based on P21 [Safety Mode] value.20 = P58 [DM Input Type] value not legal based on P20 [Cascaded Config] andP21 [Safety Mode] value.21 = P54 [Enable SW In Typ] value not legal based on P21 [Safety Mode] value.22 = P60 [Lock Mon In Type] value not legal based on P21 [Safety Mode] valueand P59 [Lock Mon Enable] value.23 = Illegal P20 [Cascaded Config] value.24 = Illegal P22 [Reset Type] value.25 = Reserved26 = Illegal P45 [Safe Stop Type] value.27 = Illegal P51 [Stop Decel Tol] value.28 = Illegal P27 [Fbk Mode] value.29 = Illegal P28 [Fbk 1 Type] value.30 = Illegal P31 [Fbk 1 Resolution] value.31 = Illegal P32 [Fbk1 Volt Mon] value.32 = Illegal P37 [Fbk 2 Volt Mon] value.33 = Illegal P24 [OverSpd Response] value.34 = Reserved36 = Unknown error (Unknown Err).Default:Options:RW Real72 SS Out ModeDefines whether the SS_Out output is pulse-tested.If pulse-testing is turned off for any output, the SIL, Category, and PL rating isreduced for the entire <strong>PowerFlex</strong> safety system.73 SLS Out ModeDefines whether the SLS_Out output is pulse-tested.If pulse-testing is turned off for any output, the SIL, Category, and PL rating isreduced for the entire <strong>PowerFlex</strong> safety system.74 Door Out ModeDefines whether the DC_Out output is pulse-tested.If pulse-testing is turned off for any output, the SIL, Category, and PL rating isreduced for the entire <strong>PowerFlex</strong> safety system.Default:Options:0 = “Pulse test”0 = “Pulse test”1 = “No pulse test”RW RealDefault:Options:0 = “Pulse test”0 = “Pulse test”1 = “No pulse test”RW RealDefault:Options:0 = “Pulse test”0 = “Pulse test”1 = “No pulse test”RW Real<strong>PowerFlex</strong> <strong>750</strong>-<strong>Series</strong> <strong>User</strong> <strong>Manual</strong> – Publication <strong>750</strong>-UM001C-EN-P – September 2009

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!