2.5.3.5 The dry ma<strong>in</strong>s’ breech<strong>in</strong>g <strong>in</strong>lets shall be with<strong>in</strong> 18m and visible<br />

from the nearest fire eng<strong>in</strong>e accessways. Where the breech<strong>in</strong>g<br />

<strong>in</strong>lets are located at the vent shafts, the design shall be such<br />

that the fire-fight<strong>in</strong>g operation near the breech<strong>in</strong>g <strong>in</strong>lets is not<br />

affected by smoke exhaust<strong>in</strong>g from the vent shafts.<br />

2.5.3.6 Connect<strong>in</strong>g pipe between the <strong>in</strong>lets and the vertical run of the<br />

ma<strong>in</strong>s, where applicable, shall be kept as short as possible.<br />

2.5.3.7 Breech<strong>in</strong>g <strong>in</strong>lets shall be appropriately numbered and labelled<br />

as shown below. The total number of dry ma<strong>in</strong>s provided <strong>for</strong><br />

the station (<strong>in</strong>clud<strong>in</strong>g tunnels) shall be <strong>in</strong>dicated. The word<strong>in</strong>g<br />

shall be white on a contrast<strong>in</strong>g background.<br />

DR 1- 6<br />

CONVENTION CENTRE STATION<br />

DR 2- 6<br />

MUSEUM TO CONVENTION CENTRE<br />

UNDERGROUND TRAINWAY<br />

NORTH BOUND<br />

Breech<strong>in</strong>g <strong>in</strong>let/Dry ma<strong>in</strong> number<br />

Total number of breech<strong>in</strong>g <strong>in</strong>lets/<br />

Dry ma<strong>in</strong>s<br />

50mm high letter<strong>in</strong>g<br />

25mm high letter<strong>in</strong>g<br />

2.5.3.8 Standby fire hose shall be provided <strong>in</strong> accordance with<br />

APPENDIX F. Two standby fire hoses shall be provided at<br />

each of the land<strong>in</strong>g valves, but one standby fire hose is also<br />

acceptable if coverage is adequate.<br />

Breech<strong>in</strong>g<br />

<strong>in</strong>lets<br />

Standby fire<br />

hose<br />

<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 100