(iii) Distance between the cross-over and the nearest<br />

cross passageway shall be not less than 125m<br />

and not more than 250m.<br />

See Diagram 2.9.2.3(g)<br />

2.9.2.4 Doors to an exit shall open <strong>in</strong> the direction of exit travel except<br />

<strong>in</strong> the case of cross passageway closures. Doors to the exit<br />

access <strong>in</strong> the tra<strong>in</strong>ways shall be provided with a self-clos<strong>in</strong>g<br />

device but no lock<strong>in</strong>g device shall be provided. The <strong>for</strong>ce<br />

required to open the doors fully when applied to the latch<br />

sided shall be as low as possible, not exceed<strong>in</strong>g 220N. In<br />

addition, door and hardware shall be adequate to withstand the<br />

positive and negative pressures created by pass<strong>in</strong>g tra<strong>in</strong>s.<br />

2.9.2.5 An effective emergency egress pathway of m<strong>in</strong>imum 800mm<br />

width shall be provided. In areas with cross passageways,<br />

unobstructed access shall be provided to the cross<br />

passageways.<br />

2.9.2.6 The walk<strong>in</strong>g surfaces of the emergency egress pathway shall<br />

have a non-slip design.<br />

2.9.2.7 Where the tra<strong>in</strong>way concreted track bed serves as emergency<br />

egress pathway, it shall be nom<strong>in</strong>ally level and free of<br />

obstructions. Where signall<strong>in</strong>g equipment is located along the<br />

emergency egress pathway, ramp and plat<strong>for</strong>m shall be<br />

provided. The edges of the ramp and plat<strong>for</strong>m shall be pa<strong>in</strong>ted<br />

with bright yellow pa<strong>in</strong>t to enhance its visibility.<br />

2.9.3<br />

EXIT SIGNS AND EMERGENCY LIGHTING<br />

2.9.3.1 Exit facilities shall be suitably identified and ma<strong>in</strong>ta<strong>in</strong>ed to<br />

allow <strong>for</strong> their <strong>in</strong>tended use.<br />

2.9.3.2 Exit signs at exit staircases shall comply with the requirements<br />

as specified <strong>for</strong> stations <strong>in</strong> Cl.2.7.1.7, whereas, non-ma<strong>in</strong>ta<strong>in</strong>ed<br />

illum<strong>in</strong>ated exit signs at cross passageways shall be designed<br />

to be remotely controlled to support the evacuation strategy.<br />

2.9.3.3 Signage shall be provided to assist emergency evacuation of<br />

passengers. The signs should be reflective or illum<strong>in</strong>ated.<br />

2.9.3.4 Emergency light<strong>in</strong>g shall be provided to underground or<br />

enclosed tra<strong>in</strong>ways exceed<strong>in</strong>g 15m <strong>in</strong> length. The illum<strong>in</strong>ation<br />

level at walk<strong>in</strong>g surfaces shall not be less than 2.7 lux.<br />

Doors<br />

Emergency<br />

egress<br />

pathway<br />

Exit signs and<br />

emergency<br />

light<strong>in</strong>g<br />