2.5.4 HOSE REELS<br />
2.5.4.1 Hose reels shall be provided throughout the station <strong>in</strong>clud<strong>in</strong>g<br />
the underground l<strong>in</strong>ks lead<strong>in</strong>g to the underground station<br />
entrances except :<br />
(a) buffer areas (<strong>in</strong>clud<strong>in</strong>g plant rooms with<strong>in</strong> these areas),<br />
station plat<strong>for</strong>ms and above-ground outdoor cool<strong>in</strong>g<br />
tower enclosure;<br />
(b) ground level entrances with no habitable rooms;<br />
(b)<br />
cable (c) cable chambers and underplat<strong>for</strong>m services ducts.<br />
2.5.4.2 Water supply, location and details of <strong>in</strong>stallation <strong>for</strong> hose reels<br />
shall comply with the requirements of SS 574 except as here<strong>in</strong><br />
modified:<br />
(a) Hose reels shall be located <strong>in</strong> the follow<strong>in</strong>g order of<br />
priority:<br />
(i) adjacent to exits and protected lobbies;<br />
(ii) along exit routes; and<br />
(iii) with<strong>in</strong> rooms.<br />
(b) Where the hose reel and automatic spr<strong>in</strong>kler systems<br />
share the same water tank, the hose reel tap-off po<strong>in</strong>ts<br />
shall be above the spr<strong>in</strong>kler system’s reserve capacity.<br />
2.5.4.3 The use of copper or sta<strong>in</strong>less steel pip<strong>in</strong>gs are permissible <strong>for</strong><br />
the connection of the hose reel to the PUB ma<strong>in</strong>s.<br />
2.5.5 ELECTRICAL FIRE ALARM SYSTEM<br />
2.5.5.1 An automatic fire alarm system shall be provided <strong>in</strong> the station.<br />
<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 101