(c) Where there are more than one private hydrant that are<br />

located above reduced level 125m with<strong>in</strong> the same plot,<br />

storage and pump<strong>in</strong>g arrangements of water supply to<br />

these specified hydrants shall comply with those <strong>for</strong> wet<br />

ris<strong>in</strong>g ma<strong>in</strong>s stipulated <strong>in</strong> SS 574 and Table 2.4.4.2 -<br />

Water Supply & Storage Requirement For Private<br />

Hydrant. The water supply <strong>for</strong> hydrants shall be as<br />

follows:<br />

Table 2.4.4.2 - Water Supply & Storage<br />

Requirement For Private Hydrant<br />

M<strong>in</strong>imum runn<strong>in</strong>g pressure 2 bars<br />

M<strong>in</strong>imum flow rate based<br />

on the largest compartment<br />

floor area<br />

M<strong>in</strong>imum duration 45m<strong>in</strong>s<br />

< 1000m 2 - 38L/s<br />

< 5000m 2 - 57L/s<br />

< 10000m 2 - 76L/s<br />

(57L/s if spr<strong>in</strong>kler protected)<br />

Additional 19L/s <strong>for</strong><br />

subsequence 5000m 2<br />

2.4.4.3 All hydrant ma<strong>in</strong>s which pass through a station shall have its<br />

full length with<strong>in</strong> the station protected with fire resistance<br />

construction of at least the same fire resistance as the element<br />

of structure, provided the follow<strong>in</strong>g requirements are complied<br />

with:<br />

(a) The hydrant ma<strong>in</strong>s shall be located <strong>in</strong> common<br />

circulation spaces and driveways; i.e. they shall not<br />

pass through private or conf<strong>in</strong>ed spaces;<br />

(b) No services (except spr<strong>in</strong>kler pipes) shall be located<br />

above or cross<strong>in</strong>g over the hydrant ma<strong>in</strong>s;<br />

(c) The hydrant ma<strong>in</strong>s shall be located away from explosion<br />

risk areas; and<br />

(d) The protective enclosure to the hydrant ma<strong>in</strong>s shall be<br />

labelled with the words "HYDRANT MAIN" of<br />

m<strong>in</strong>imum 50mm height at suitable <strong>in</strong>tervals.<br />

Protection of<br />

hydrant ma<strong>in</strong>s<br />

<strong>in</strong> stations<br />