(c) Where there are more than one private hydrant that are<br />
located above reduced level 125m with<strong>in</strong> the same plot,<br />
storage and pump<strong>in</strong>g arrangements of water supply to<br />
these specified hydrants shall comply with those <strong>for</strong> wet<br />
ris<strong>in</strong>g ma<strong>in</strong>s stipulated <strong>in</strong> SS 574 and Table 2.4.4.2 -<br />
Water Supply & Storage Requirement For Private<br />
Hydrant. The water supply <strong>for</strong> hydrants shall be as<br />
follows:<br />
Table 2.4.4.2 - Water Supply & Storage<br />
Requirement For Private Hydrant<br />
M<strong>in</strong>imum runn<strong>in</strong>g pressure 2 bars<br />
M<strong>in</strong>imum flow rate based<br />
on the largest compartment<br />
floor area<br />
M<strong>in</strong>imum duration 45m<strong>in</strong>s<br />
< 1000m 2 - 38L/s<br />
< 5000m 2 - 57L/s<br />
< 10000m 2 - 76L/s<br />
(57L/s if spr<strong>in</strong>kler protected)<br />
Additional 19L/s <strong>for</strong><br />
subsequence 5000m 2<br />
2.4.4.3 All hydrant ma<strong>in</strong>s which pass through a station shall have its<br />
full length with<strong>in</strong> the station protected with fire resistance<br />
construction of at least the same fire resistance as the element<br />
of structure, provided the follow<strong>in</strong>g requirements are complied<br />
with:<br />
(a) The hydrant ma<strong>in</strong>s shall be located <strong>in</strong> common<br />
circulation spaces and driveways; i.e. they shall not<br />
pass through private or conf<strong>in</strong>ed spaces;<br />
(b) No services (except spr<strong>in</strong>kler pipes) shall be located<br />
above or cross<strong>in</strong>g over the hydrant ma<strong>in</strong>s;<br />
(c) The hydrant ma<strong>in</strong>s shall be located away from explosion<br />
risk areas; and<br />
(d) The protective enclosure to the hydrant ma<strong>in</strong>s shall be<br />
labelled with the words "HYDRANT MAIN" of<br />
m<strong>in</strong>imum 50mm height at suitable <strong>in</strong>tervals.<br />
Protection of<br />
hydrant ma<strong>in</strong>s<br />
<strong>in</strong> stations<br />