2.6.5<br />

(ix) The exhaust fan shall be capable of operat<strong>in</strong>g<br />

effectively at 250ºC <strong>for</strong> 2 hours and supplied<br />

from a secondary source of supply.<br />

(x) Replacement air shall be provided and if it is<br />

supplied by a separate mechanical system, such a<br />

system shall be connected to a secondary source<br />

of power.<br />

(d) The smoke purg<strong>in</strong>g system need not be a dedicated<br />

system. Where dampers are used to direct the smoke<br />

<strong>for</strong> the smoke purg<strong>in</strong>g system, motorised smoke<br />

dampers shall be used.<br />

(e) Shops as permitted <strong>in</strong> Cl. 2.1.3 are not required to be<br />

provided with smoke control system.<br />

(f) Public area outside the commercial space shall be<br />

provided with smoke purg<strong>in</strong>g system as shown <strong>in</strong><br />

Diagram 2.6.4.1(f).<br />

(g) The smoke purg<strong>in</strong>g system <strong>in</strong> the station public area<br />

shall be automatically activated by detectors located <strong>in</strong><br />

the station public areas. Similarly the smoke purg<strong>in</strong>g<br />

system <strong>in</strong> a non-public area shall be activated by the<br />

fire alarm signals from that particular non-public area.<br />

UNDERGROUND AND ENCLOSED STATION<br />

TRAINWAY EMERGENCY VENTILATION SYSTEM<br />

2.6.5.1 An emergency ventilation system shall be designed <strong>for</strong> a tra<strong>in</strong><br />

fire <strong>in</strong> an underground and enclosed stations tra<strong>in</strong>way as<br />

follows:<br />

(a) Provide a tenable environment along the path of egress<br />

from the fire <strong>in</strong>cident.<br />

(b) Be capable of reach<strong>in</strong>g full operational status <strong>in</strong> 120<br />

seconds or less.<br />

(c) The emergency ventilation fans shall be provided such<br />

that <strong>in</strong> the event one of the fans is not operational, the<br />

other fan(s) shall be capable of ma<strong>in</strong>ta<strong>in</strong><strong>in</strong>g the system<br />

design.<br />

(d) The replacement air velocity aga<strong>in</strong>st the direction of<br />

escape at doorways and escape routes shall not exceed<br />

5m/s<br />

Shops<br />

Replacement<br />

air<br />

<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 115