2.6.2.2 The mechanical ventilation systems <strong>for</strong> stations and staircase<br />
pressurisation where required under Cl.2.2.5.6 shall comply<br />
with SS 553 Code of Practice <strong>for</strong> Mechanical Ventilation and<br />
Air-condition<strong>in</strong>g <strong>in</strong> Build<strong>in</strong>gs, unless as here<strong>in</strong> modified.<br />
(a) The mechanical ventilation of the firemen’s staircase<br />
shall be ma<strong>in</strong>ta<strong>in</strong>ed at higher positive pressure with<br />
respect to the mechanical ventilation system of the<br />
adjacent fire-fight<strong>in</strong>g lobby.<br />
(b) Duct cover<strong>in</strong>gs, duct l<strong>in</strong><strong>in</strong>gs and flexible connection<br />
materials shall be non-combustible. However, if it is<br />
necessary to use combustible materials, it shall have a<br />
surface flame spread rat<strong>in</strong>g of not lower than Class 0.<br />
(c) (i) Thermal <strong>in</strong>sulation materials <strong>for</strong> pipework<br />
together with vapour barrier l<strong>in</strong><strong>in</strong>gs and<br />
adhesives shall have a surface flame spread of<br />
not lower than Class 0.<br />
(ii) Notwithstand<strong>in</strong>g the requirements of sub-clause<br />
(c)(i), the use of plastic and foam rubber<br />
<strong>in</strong>sulation materials of a lower classification is<br />
permissible only <strong>in</strong> above-ground stations if:<br />
* The material is the self ext<strong>in</strong>guish<strong>in</strong>g type;<br />
* The <strong>in</strong>sulation material is covered by or<br />
encased <strong>in</strong> a metal sheath or hybrid plaster<br />
or other non-combustible cladd<strong>in</strong>g material.<br />
[Note: Any open<strong>in</strong>g <strong>in</strong> the element of structure or<br />
other part of a build<strong>in</strong>g penetrated by the<br />
pipework shall be effectively fire-stopped by<br />
replacement of the <strong>in</strong>sulation material at the<br />
junction of penetration with fire resistant<br />
material hav<strong>in</strong>g equal fire rat<strong>in</strong>g.]<br />
(d) Rooms hav<strong>in</strong>g no other usage than hous<strong>in</strong>g air<br />
handl<strong>in</strong>g equipment or package units and their<br />
associated electrical controls are not regarded as areas<br />
of high risk.<br />
<strong>Fire</strong>men’s<br />
staircase<br />
Duct cover<strong>in</strong>g,<br />
duct l<strong>in</strong><strong>in</strong>g and<br />
flexible<br />
connection<br />
Pipework<br />
Insulation<br />
Plastic and<br />
foam rubber<br />
<strong>in</strong>sulation<br />
Air handl<strong>in</strong>g<br />
unit rooms<br />
<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 111