(c) <strong>Fire</strong> doors or shutters held open by electromagnetic or<br />

electro-mechanical devices shall be activated to close by<br />

the localized smoke detector(s) on either (one) side of<br />

the fire doors or shutters, and<br />

Exemption: <strong>Fire</strong> shutters <strong>in</strong> non-public areas (i.e.<br />

activated by fusible l<strong>in</strong>k only).<br />

(d) Use of fire shutter not exceed<strong>in</strong>g 6m <strong>in</strong> width shall be<br />

permitted.<br />

(e) Any fire door fitted <strong>in</strong> an open<strong>in</strong>g which is provided as<br />

a means of escape:<br />

(i) Shall be capable of be<strong>in</strong>g opened manually, and<br />

(ii) Shall not be held open by any means other than<br />

by an electromagnetic or electro-mechanical<br />

device which can be activated by the presence of<br />

smoke and/or the fire alarm system, provided that<br />

this shall not apply <strong>in</strong> the case of fire doors<br />

open<strong>in</strong>g <strong>in</strong>to pressurised exit staircases, and<br />

(iii) Shall open <strong>in</strong> the direction of exit travel <strong>in</strong><br />

accordance with Cl. 2.2.5.13(d).<br />

(f) <strong>Fire</strong> resist<strong>in</strong>g doors where required to be provided shall<br />

be constructed and <strong>in</strong>stalled to comply with<br />

specifications stipulated under SS 332 Specification<br />

<strong>for</strong> <strong>Fire</strong> Doors and SS 489 Specification <strong>for</strong> <strong>Fire</strong><br />

Shutters.<br />

(g) <strong>Fire</strong> shutters shall not be used as security shutters.<br />

(h) The <strong>in</strong>active leaf of double-leaf doors <strong>for</strong><br />

plant/equipment/mach<strong>in</strong>e rooms and <strong>for</strong><br />

lobby/corridor lead<strong>in</strong>g to these rooms, where the<br />

<strong>in</strong>active leaf is only <strong>for</strong> use as equipment access, need<br />

not be fitted with a self-clos<strong>in</strong>g device, but must be<br />

bolted <strong>in</strong> place and fitted with a sign “Keep door<br />

bolted”.<br />

<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 67