2.3.9.3 Pipes<br />
(a) Pipes which pass through a separat<strong>in</strong>g wall,<br />
compartment wall or compartment floor shall be kept<br />
as small as possible and fire-stopped around the pipe.<br />
The nom<strong>in</strong>al <strong>in</strong>ternal diameter of the pipe shall be not<br />
more than the relevant dimension given <strong>in</strong> Table<br />
2.3.9A with the exception of pipes hav<strong>in</strong>g the<br />
necessary fire resistance when tested to BS 476: Part<br />
20 or other acceptable standards. Clear spac<strong>in</strong>g<br />
between pipes shall be m<strong>in</strong>imum 50mm or ½-diameter<br />
of the largest pipe, whichever is the larger.<br />
Exception: Emergency standby diesel generator steel<br />
exhaust pipes connected directly to the external.<br />
(b) In additional to sub-clause (a), fuel and vent pipes <strong>for</strong><br />
emergency standby diesel generators and fuel tanks<br />
located outside the room they served shall be enclosed<br />
<strong>in</strong> construction hav<strong>in</strong>g fire resistance of not less than 2<br />
hours. They shall not be located <strong>in</strong> <strong>in</strong>take/fresh air vent<br />
shaft.<br />
2.3.9.4 Ventilation duct which passes directly through a<br />
compartment wall or compartment floor shall comply with<br />
the follow<strong>in</strong>g -<br />
(a) Where the ventilation duct does not <strong>for</strong>m a protected<br />
shaft or is not conta<strong>in</strong>ed with<strong>in</strong> a protect<strong>in</strong>g structure,<br />
(i) The duct shall be fitted with a fire damper where<br />
it passes through the compartment wall or<br />
compartment floor, and<br />
(ii) The open<strong>in</strong>g <strong>for</strong> the duct shall be kept as small as<br />
practicable and any gap around the fire damper<br />
shall be fire-stopped.<br />
(b) Where the ventilation duct <strong>for</strong>ms a protected shaft or is<br />
conta<strong>in</strong>ed with<strong>in</strong> a protect<strong>in</strong>g structure, the duct shall<br />
be:<br />
(i) Fitted with fire dampers at the <strong>in</strong>lets to the shaft<br />
and outlets from it, and<br />
(ii) Constructed and l<strong>in</strong>ed with materials <strong>in</strong><br />
accordance with the requirements <strong>in</strong> Section 2.6.<br />
(c) The <strong>in</strong>stallation of ventilation ducts and fire dampers<br />
shall comply with the requirements <strong>in</strong> Section 2.6.<br />
Pipes<br />
Ventilation<br />
ducts<br />