2.4.1 GENERAL<br />

SECTION 2.4<br />

SITE PLANNING & EXTERNAL<br />

FIRE FIGHTING PROVISION FOR STATIONS<br />

2.4.1.1 The purpose of this Section of the <strong>Standard</strong> is to make<br />

provision <strong>for</strong> space around stations to enable effective<br />

mount<strong>in</strong>g of rescue and external fire fight<strong>in</strong>g operations.<br />

2.4.2 PROVISION FOR EXTERNAL ACCESS TO STATION<br />

FOR FIRE FIGHTING AND ACCESSIBILITY OF SITE<br />

TO FIRE FIGHTING APPLIANCES<br />

2.4.2.1 Access open<strong>in</strong>gs along external walls of stations, firemen's<br />

staircase <strong>for</strong> underground stations, fire eng<strong>in</strong>e accessway and<br />

fire eng<strong>in</strong>e access road shall be provided <strong>for</strong> fire fight<strong>in</strong>g and<br />

rescue operations.<br />

Exception: Access open<strong>in</strong>g and fire eng<strong>in</strong>e accessway are not<br />

required <strong>for</strong> s<strong>in</strong>gle storey structure of stations<br />

above ground level.<br />

2.4.2.2 ACCESS OPENING<br />

(a) Open<strong>in</strong>gs on the external wall <strong>for</strong> external fire fight<strong>in</strong>g<br />

and rescue operation. Access open<strong>in</strong>gs shall <strong>in</strong>clude<br />

unobstructed external wall open<strong>in</strong>gs, w<strong>in</strong>dows, glazed<br />

wall panels or access panels. W<strong>in</strong>dows, doors, wall<br />

panels or access panels must be readily openable from<br />

the <strong>in</strong>side and outside, unless fitted by breakable<br />

glaz<strong>in</strong>g. Inside and outside of access open<strong>in</strong>gs shall be<br />

unobstructed at all times dur<strong>in</strong>g the occupancy of the<br />

station.<br />

(b) Where an external wall which faces the accessway has<br />

external open<strong>in</strong>gs on each storey level that meet the<br />

requirements of sub-clauses below, there is no need to<br />

designate any access open<strong>in</strong>g.<br />

(c) Panels to access open<strong>in</strong>gs shall be posted with either a<br />

red or orange triangle of equal sides (m<strong>in</strong>imum 150mm<br />

on each side), which can be upright or <strong>in</strong>verted, on the<br />

external side of the wall and with word<strong>in</strong>gs "<strong>Fire</strong><br />

Fight<strong>in</strong>g Access - Do Not Obstruct" of at least 25mm<br />

height on the <strong>in</strong>ternal side.<br />

General<br />

Introduction<br />

Access<br />

open<strong>in</strong>gs <strong>for</strong><br />

above-ground<br />

stations<br />

Signage<br />

<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 84