(b) Where the lift shaft is not a protected shaft, the lift<br />

hoistway shall be adequately ventilated at the top of<br />

the shaft by means of one or more permanent open<strong>in</strong>gs<br />

hav<strong>in</strong>g a total unobstructed area of not less than 0.1m 2<br />

<strong>for</strong> each lift <strong>in</strong> the shaft.<br />

2.6.3 ENGINEERED SMOKE CONTROL SYSTEM<br />

2.6.3.1 Eng<strong>in</strong>eered smoke control system shall be provided <strong>in</strong><br />

basement commercial space on commercial floor and shall<br />

comply with SS 553 Code of Practice <strong>for</strong> Mechanical<br />

ventilation and air-condition<strong>in</strong>g <strong>in</strong> build<strong>in</strong>gs.<br />

2.6.3.2 The eng<strong>in</strong>eered smoke control system need not be a dedicated<br />

system.<br />

2.6.3.3<br />

In lieu of smoke detectors, l<strong>in</strong>ear heat detectors of the optic<br />

fibre type can be used to activate the eng<strong>in</strong>eered smoke control<br />

systems <strong>in</strong> non-public areas.<br />

2.6.4 SMOKE PURGING SYSTEM<br />

2.6.4.1 Underground Station Public And Ancillary Areas<br />

(a) Smoke purg<strong>in</strong>g system shall be provided <strong>in</strong> the<br />

follow<strong>in</strong>g areas:-<br />

(i) Station public areas<br />

(ii) Corridors of ancillary areas <strong>in</strong> basement.<br />

Except the follow<strong>in</strong>g:-<br />

(iii) Corridors serv<strong>in</strong>g only ticket<strong>in</strong>g mach<strong>in</strong>e<br />

rooms, staff offices, staff toilets, cleaner's stores and<br />

not more than one plantroom.<br />

(iv) Corridor at buffer areas.<br />

(b) For underground station with enclosed public areas<br />

above ground, the smoke purg<strong>in</strong>g system shall be<br />

extended to these public areas.<br />

Station public<br />

areas and<br />

corridors<br />

<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 113