(a) If two exits or exit access doors are required, they<br />

shall be placed at a distance from one another<br />

equal to or not less than half the length of the<br />

maximum overall diagonal dimension of the<br />

compartment or area to be served, measured <strong>in</strong> a<br />

straight l<strong>in</strong>e between the furthest edges of the exit<br />

doors or exit access doors (see Diagram<br />

2.2.5.16(a)(i) to (a)(v)). If the distance between the<br />

2 exits is less than half the length of the maximum<br />

overall diagonal dimension of the compartment or<br />

area to be served, it shall be considered as a oneway<br />

escape arrangement.<br />

(b) In rooms or compartments protected throughout by<br />

an approved automatic spr<strong>in</strong>kler system which<br />

complies with the requirements of Section 2.5, the<br />

m<strong>in</strong>imum separation distance between two exits or<br />

exit access doors measured <strong>in</strong> accordance with<br />

Cl. 2.2.5.16(a) shall be not less than one third the<br />

length of the maximum overall diagonal dimension<br />

of the compartment or area to be served.<br />

(c) Where exits are <strong>in</strong>ter-connected by a corridor, exit<br />

separation shall be permitted to be measured along<br />

the l<strong>in</strong>e of travel with<strong>in</strong> the exit access corridor.<br />

The exit access corridor connect<strong>in</strong>g the exits shall<br />

be protected by m<strong>in</strong>imum 1-hour fire rated<br />

enclosures. Doors open<strong>in</strong>g <strong>in</strong>to this corridor shall<br />

have m<strong>in</strong>imum ½-hour fire resistance rat<strong>in</strong>g (see<br />

Diagram 2.2.5.16(c)).<br />

2.2.5.17 Exits shall be provided with artificial light<strong>in</strong>g facilities to<br />

the satisfaction of the requirements <strong>in</strong> Section 2.7.<br />

2.2.5.18 The location of every exit on every floor shall be clearly<br />

<strong>in</strong>dicated by exit sign and directional signs to comply with<br />

the requirements <strong>in</strong> Section 2.7.<br />