26.03.2013 Views

Standard for Fire Safety in Rapid Transit Systems - Singapore Civil ...

Standard for Fire Safety in Rapid Transit Systems - Singapore Civil ...

Standard for Fire Safety in Rapid Transit Systems - Singapore Civil ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

APPENDIX F<br />

STANDBY FIRE HOSE FOR RISING MAIN<br />

F.1 Type and fold<strong>in</strong>g method<br />

F.1.1 The standby fire hose shall be of 63.5mm nom<strong>in</strong>al <strong>in</strong>ternal<br />

diameter <strong>in</strong> order to ensure that the hose coupl<strong>in</strong>g will fit<br />

exist<strong>in</strong>g coupl<strong>in</strong>g tail pieces. The hose shall be rugged and<br />

capable of carry<strong>in</strong>g water under substantive pressure <strong>in</strong><br />

accordance with BS 6391. The fire hose shall be of type 3 as<br />

stipulated <strong>in</strong> BS 6391.<br />

F.1.2 The fire hose coupl<strong>in</strong>gs shall be manufactured to BS<br />

specification or equivalent and of light alloy or gunmetal.<br />

The coupl<strong>in</strong>g shall be of type 63.5mm and be of the<br />

<strong>in</strong>stantaneous type with standard (double-pull) release<br />

mechanism. The coupl<strong>in</strong>gs shall be tied <strong>in</strong> by b<strong>in</strong>d<strong>in</strong>g with<br />

galvanised mild steel wire and applied over a hose guard of<br />

synthetic fibre. It shall be able to withstand a m<strong>in</strong>imum<br />

work<strong>in</strong>g pressure of 15 bars.<br />

F.1.3 Each hose shall have a standard length of 30m and shall be<br />

kept stowed <strong>in</strong> a Dutch Rolled position and housed <strong>in</strong> a glassfronted<br />

cab<strong>in</strong>et.<br />

F.2 Position<br />

F.2.1 The fire hose shall be <strong>in</strong>stalled just next to, but not more than<br />

2m from the land<strong>in</strong>g valve.<br />

F.2.2 The entire fire hose and cab<strong>in</strong>et shall be out of direct sunlight.<br />

F.3 Mount<strong>in</strong>g<br />

The wall mounted fire hose cab<strong>in</strong>et requirement shall be as<br />

follows:<br />

(i) The cab<strong>in</strong>et shall be firmly mounted on the wall and<br />

rigid to take either one or two fire hose weight.<br />

(ii) The cab<strong>in</strong>et shall be constructed of non-combustible<br />

material.<br />

(iii) The cab<strong>in</strong>et lock, if provided, shall be of the type that<br />

could be operated manually from the <strong>in</strong>side without<br />

the use of a key when the front pla<strong>in</strong> glass/plastic<br />

(m<strong>in</strong>imum 300mm x 300mm) is broken by the fire<br />

fighter.<br />

Type<br />

Hose<br />

coupl<strong>in</strong>gs<br />

Storage<br />

<strong>Fire</strong> hose<br />

cab<strong>in</strong>et<br />

<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> F-1

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!