2.8.4 STATIONS CONNECTED TO NON-TRANSIT<br />

OCCUPANCIES<br />

2.8.4.1 Where an entrance of an underground station is <strong>in</strong>tegrated with<br />

a non-transit occupancy, the follow<strong>in</strong>g shall be complied with:<br />

(a) The entrance shall comply with the relevant fire safety<br />

requirements <strong>in</strong> other sections of this <strong>Standard</strong>.<br />

(b) The entrance shall be fire separated from the non-transit<br />

occupancy with fire barriers hav<strong>in</strong>g at least 2 hours fire<br />

resistance.<br />

(c) There shall be no unprotected open<strong>in</strong>gs at the nontransit<br />

occupancy area with<strong>in</strong> 3m of the ventilation<br />

open<strong>in</strong>gs located <strong>in</strong> the external wall of the entrance.<br />

(d) Where fire-rated shutters are <strong>in</strong>stalled to provide the fire<br />

separation required <strong>in</strong> Cl.2.8.4.1(b), it shall be <strong>in</strong>stalled<br />

with localised smoke detector on both sides of the fire<br />

rated shutter. These fire-rated shutters shall be activated<br />

by:<br />

- the localised smoke detector/s on either side (ie. one<br />

side) of these fire shutters,<br />

- the adjacent build<strong>in</strong>g fire alarm zones <strong>in</strong> adjacent<br />

build<strong>in</strong>g.<br />

Upon activation of the localized standalone smoke<br />

detector, an alarm signal shall be sent to the fire alarm<br />

panels of both the station & the adjacent build<strong>in</strong>g.<br />

Where motorised fire-rated shutters are provided, the<br />

fire-rated shutters after clos<strong>in</strong>g shall rema<strong>in</strong> closed and<br />

be rendered <strong>in</strong>operative until the alarm has been reset.<br />

Note: This alarm signal is not used to trigger the<br />

build<strong>in</strong>g fire alarm but is <strong>in</strong>tended to provide the status<br />

that the shutter is activated and is used as a means to<br />

reset the fire alarm panel to reopen the fire shutter after<br />

its activation. There<strong>for</strong>e, the smoke detector located at<br />

the side of the shutter is not part of the build<strong>in</strong>g fire<br />

alarm.<br />

(e) Use of fire shutter not exceed<strong>in</strong>g 6m <strong>in</strong> width is<br />

permitted.<br />

Station<br />

entrance<br />

<strong>Fire</strong> separation<br />

Unprotected<br />

open<strong>in</strong>gs<br />

<strong>Fire</strong>-rated<br />

shutters<br />

<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 131