(d) Access open<strong>in</strong>gs shall be not less than 850 mm wide by<br />

1000 mm high with sill height of not more than 1100<br />

mm and head height not less than 1800 mm above the<br />

<strong>in</strong>side floor level.<br />

(e) Number and position of access open<strong>in</strong>gs:<br />

i) Access open<strong>in</strong>gs shall be spaced at not more than<br />

20m apart measured along the external wall from<br />

centre to centre of the access open<strong>in</strong>gs.<br />

ii) For stations with an area or space that has a<br />

ceil<strong>in</strong>g height greater than 10m, high level access<br />

open<strong>in</strong>gs <strong>for</strong> smoke vent<strong>in</strong>g and fire fight<strong>in</strong>g<br />

purposes shall be provided and located <strong>in</strong> the<br />

external walls open<strong>in</strong>g <strong>in</strong>to the area or space.<br />

2.4.2.3 FIREMEN'S STAIRCASE<br />

(a) At least one firemen’s staircase shall be provided <strong>for</strong><br />

every underground station.<br />

(b) The entrance to firemen's staircase on the ground level<br />

shall be visible and with<strong>in</strong> 18m from a fire eng<strong>in</strong>e<br />

access road.<br />

(c) <strong>Fire</strong>men’s staircase shall have access to every<br />

basement storey via fire-fight<strong>in</strong>g lobbies.<br />

(d) <strong>Fire</strong>-fight<strong>in</strong>g lobby shall not be used <strong>for</strong> any other<br />

purposes and the size of the fire-fight<strong>in</strong>g lobby shall<br />

not be smaller than 6m² and with no dimension smaller<br />

than 2m. Where the fire-fight<strong>in</strong>g lobby has a fire lift<br />

provided under Cl.2.5.7.4(c), the floor shall be graded<br />

from the lift door towards the lobby door with a fall<br />

not exceed<strong>in</strong>g 1 <strong>in</strong> 200.<br />

2.4.2.4 ACCESSWAY FOR FIRE FIGHTING APPLIANCES<br />

(a) i) Accessway shall be provided <strong>for</strong> accessibility of<br />

site to fire fight<strong>in</strong>g appliances. To permit firefight<strong>in</strong>g<br />

appliances to be deployed, the accessway<br />

shall have a m<strong>in</strong>imum width of 6m throughout its<br />

entire length. Access open<strong>in</strong>gs shall be provided<br />

along the external walls of station front<strong>in</strong>g the<br />

accessway to provide access <strong>in</strong>to the station <strong>for</strong><br />

fire fight<strong>in</strong>g and rescue operations.<br />

<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 85<br />

Size<br />

Position<br />

Additional<br />

open<strong>in</strong>gs<br />

<strong>Fire</strong>men’s<br />

staircase <strong>for</strong><br />

underground<br />

stations<br />