2.9.3.5 The emergency light<strong>in</strong>g shall be connected to an emergency<br />
power supply capable of ma<strong>in</strong>ta<strong>in</strong><strong>in</strong>g the m<strong>in</strong>imum<br />
illum<strong>in</strong>ation level <strong>for</strong> at least 2 hours.<br />
2.9.3.6 <strong>Fire</strong> resistant cables of m<strong>in</strong>imum 2-hour rat<strong>in</strong>g shall be used.<br />
2.9.4 FIRE PROTECTION<br />
2.9.4.1 Underground or enclosed tra<strong>in</strong>ways shall be provided with dry<br />
ma<strong>in</strong>s. The dry ma<strong>in</strong> system and its associated water supply,<br />
control and test<strong>in</strong>g requirements shall be <strong>in</strong>stalled <strong>in</strong><br />
accordance with SS 574, except as here<strong>in</strong> modified:<br />
(a) Dry ma<strong>in</strong> system shall be provided <strong>in</strong> accordance with<br />
Diagram 2.9.4.1(a) <strong>for</strong> the follow<strong>in</strong>g areas:<br />
i) Each underground tra<strong>in</strong>way located between two<br />
stations;<br />
ii) Each underground or enclosed tra<strong>in</strong>way between a<br />
station and the tra<strong>in</strong>way portal; and<br />
iii) Each underground or enclosed reception or test<br />
track.<br />
(b) For over-run tra<strong>in</strong>way, the dry ma<strong>in</strong> system can be<br />
served with only one breech<strong>in</strong>g <strong>in</strong>let at the station end.<br />
(c) The nom<strong>in</strong>al bore of the dry ma<strong>in</strong> shall not be less than<br />
150mm.<br />
(d) The dry ma<strong>in</strong>s <strong>in</strong> the tra<strong>in</strong>ways need not be fire-rated.<br />
(e) Land<strong>in</strong>g valves shall be located at not less than 2m and<br />
not more than 3m from exit staircases and cross<br />
passageways and shall be spaced at <strong>in</strong>tervals not<br />
exceed<strong>in</strong>g 60m along the tra<strong>in</strong>way.<br />
(f) The first land<strong>in</strong>g valve of the dry ma<strong>in</strong> after the<br />
breech<strong>in</strong>g <strong>in</strong>let shall be located not exceed<strong>in</strong>g 3m from<br />
the <strong>in</strong>terface of the station box and the tra<strong>in</strong>way. For the<br />
case of Cl.2.9.4.1(a)(ii), the first land<strong>in</strong>g valve after the<br />
breech<strong>in</strong>g <strong>in</strong>let shall be located not more than 3m from<br />
the portal.<br />
(g) Where gaskets are used <strong>in</strong> pipe jo<strong>in</strong>ts <strong>for</strong> dry ma<strong>in</strong>s<br />
serv<strong>in</strong>g different tra<strong>in</strong>ways but located <strong>in</strong> common TV<br />
vent shaft and TVF fan room, the gaskets shall be<br />
suitable <strong>for</strong> use <strong>in</strong> an ambient atmosphere of 250C.<br />