2.6.5.9 Smoke reservoirs shall be provided above the station tra<strong>in</strong>ways<br />

and plat<strong>for</strong>m screen doors (PSD). The materials used <strong>for</strong> the<br />

construction of the smoke reservoirs shall be able to withstand<br />

the designed highest temperature from a tra<strong>in</strong> fire or hav<strong>in</strong>g a<br />

fire resistance rat<strong>in</strong>g of not less than 2 hours.<br />

Smoke<br />

reservoirs<br />

<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 117