(e) Where the supply air duct serv<strong>in</strong>g the exit staircase has<br />
to penetrate the staircase enclosure, the portion of the<br />
duct where it traverses outside the staircase shall be<br />
enclosed <strong>in</strong> masonry construction or drywall<br />
comply<strong>in</strong>g with Cl.2.3.8.7(c) of at least the same fire<br />
resistance as the elements of structure and it shall not<br />
be fitted with fire dampers.<br />
(f) Where duct risers are required to be enclosed <strong>in</strong><br />
protected shafts, the protected shafts shall be enclosed<br />
<strong>in</strong> masonry construction or drywall comply<strong>in</strong>g with<br />
Cl.2.3.8.7(c).<br />
(g) Battery rooms shall be ventilated to ma<strong>in</strong>ta<strong>in</strong> the<br />
average hydrogen concentration by volume <strong>in</strong> the room<br />
below 2%.<br />
(h) Magnetic (short circuit) trips are permitted <strong>for</strong> use <strong>in</strong><br />
motor circuits of essential mechanical ventilation<br />
systems and equipment. Moulded Case Circuit<br />
Breakers (MCCBs) with magnetic release only are<br />
permitted <strong>for</strong> use <strong>in</strong> lieu of High Ruptur<strong>in</strong>g Capacity<br />
(HRC) fuses.<br />
2.6.2.3 <strong>Fire</strong> dampers shall not be fitted <strong>in</strong> the follow<strong>in</strong>g locations:<br />
(a) Open<strong>in</strong>gs <strong>for</strong> ducts of emergency ventilation systems<br />
<strong>in</strong> walls of ventilation shaft.<br />
(b) Anywhere <strong>in</strong> an air pressuris<strong>in</strong>g system.<br />
2.6.2.4 Vent Open<strong>in</strong>gs <strong>in</strong> Lift Hoistway<br />
(a) The protected lift shaft shall be vented <strong>in</strong> accordance<br />
with SS 550 Code of Practice <strong>for</strong> Installation,<br />
Operation and Ma<strong>in</strong>tenance of Electric Passenger and<br />
Goods Lifts. The vents shall be so arranged as to<br />
<strong>in</strong>duce exhaust ventilation of the shaft. Where vents<br />
could not be provided because of the location of the<br />
lift shaft, ventilation duct protected by drywall<br />
comply<strong>in</strong>g with Cl.2.3.8.8(b) serv<strong>in</strong>g as ventilation of<br />
the shaft may be provided <strong>in</strong>stead. If the duct is not to<br />
be fire rated, fire dampers shall be provided to the duct<br />
at the wall of the lift shaft, provided such relaxation<br />
shall not apply to shaft conta<strong>in</strong><strong>in</strong>g fire lift.<br />
Prohibition of<br />
fire dampers<br />
Hoistway<br />
ventilation<br />
<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 112