2.6.1 GENERAL<br />
SECTION 2.6<br />
STATION SMOKE CONTROL AND<br />
MECHANICAL VENTILATION SYSTEMS<br />
2.6.1.1 Fans <strong>for</strong>m<strong>in</strong>g part of a fire rated duct shall also be enclosed <strong>in</strong><br />
the same fire rated enclosure.<br />
2.6.1.2 Ductwork not serv<strong>in</strong>g smoke control fan rooms shall not pass<br />
through the smoke control fan rooms.<br />
2.6.1.3 PVC pipes are prohibited <strong>in</strong> underground stations, except PVC<br />
pipe sleeves and condensate dra<strong>in</strong> pipes <strong>for</strong> air-condition<strong>in</strong>g<br />
units as stipulated <strong>in</strong> Cl.2.3.15.11 of this <strong>Standard</strong>.<br />
2.6.1.4 Fresh/exhaust air of the station’s smoke control and<br />
mechanical ventilation systems can be taken from/discharge to<br />
the <strong>in</strong>take/exhaust air shafts (shown shaded <strong>in</strong> Diagrams<br />
2.6.1.4(a) and 2.6.1.4(b)) respectively of the underground<br />
station.<br />
2.6.1.5 The <strong>in</strong>take and exhaust air shafts shall be positioned or<br />
protected to prevent re-circulation of smoke <strong>in</strong>to the system<br />
through air <strong>in</strong>take open<strong>in</strong>gs, station entrances and other surface<br />
open<strong>in</strong>gs. Adjacent structures and property uses also shall be<br />
considered.<br />
2.6.1.6 Primary and secondary power supply shall comply with<br />
Cl.4.1.3 of this <strong>Standard</strong>.<br />
2.6.1.7 Where replacement air is taken from doorways at station<br />
entrances, devices or other measures shall be <strong>in</strong>corporated to<br />
admit replacement air upon activation of the emergency<br />
ventilation system to achieve the design requirements dur<strong>in</strong>g<br />
operat<strong>in</strong>g hours and non-operat<strong>in</strong>g hours when the station is<br />
closed <strong>for</strong> passenger service.<br />
2.6.2 AIR-CONDITIONING & MECHANICAL<br />
VENTILATION SYSTEMS<br />
2.6.2.1 Where air-condition<strong>in</strong>g system is provided <strong>in</strong> lieu of<br />
mechanical ventilation system dur<strong>in</strong>g emergency, all the<br />
requirements specified <strong>in</strong> this <strong>Standard</strong> <strong>for</strong> the mechanical<br />
ventilation system shall apply to the air-condition<strong>in</strong>g system.<br />
Smoke control<br />
fan rooms<br />
PVC pipes<br />
Air shafts<br />
Re-circulation<br />
of smoke<br />
Power supply<br />