B.1.7 Where exit paths divide, i.e., where a choice of exit paths is<br />

presented, it is presumed that the passengers will divide <strong>in</strong>to<br />

groups roughly <strong>in</strong> proportion to the exit capacity provided by<br />

the various paths at the decision po<strong>in</strong>t. It also is presumed<br />

that passengers, once hav<strong>in</strong>g made a decision (select<strong>in</strong>g an<br />

exit path), will stay on that path until another decision po<strong>in</strong>t<br />

is reached or egress is achieved.<br />

B.1.8 The wait<strong>in</strong>g time at each of the various circulation elements<br />

is calculated, <strong>for</strong> the plat<strong>for</strong>m exits, by subtract<strong>in</strong>g the<br />

walk<strong>in</strong>g travel time on the plat<strong>for</strong>m from the plat<strong>for</strong>m exits<br />

flow time, and <strong>for</strong> each of the rema<strong>in</strong><strong>in</strong>g circulation elements,<br />

by subtract<strong>in</strong>g the maximum of all previous element flow<br />

times.<br />

B.2 CENTRE PLATFORM STATION<br />

B.2.1 The sample centre plat<strong>for</strong>m station shown <strong>in</strong> Figure B-2.1 is<br />

an underground station with the concourse above the<br />

plat<strong>for</strong>m level but below grade. The plat<strong>for</strong>m public area is<br />

60m long to accommodate the tra<strong>in</strong> length. The vertical<br />

distance from the plat<strong>for</strong>m to the concourse is 5m. The<br />

vertical distance from concourse to grade is 8m.<br />

The station has two entrances normally used by passengers.<br />

Each of these entrances has two escalators of 1m clear width<br />

and one stair of 2m clear width. The entrances are covered at<br />

grade level to a po<strong>in</strong>t 9m beyond the top of the stair land<strong>in</strong>g.<br />

The station concourse level has one paid area separated from<br />

the unpaid area. At two ends of the paid area, there are 8<br />

electronic fare gates and a 1-m wide emergency gate. The<br />

open well at the centre of the concourse level communicate<br />

with the plat<strong>for</strong>m level. Each end has one stair of 2m clear<br />

width and two escalators of 1m clear width. Station ancillary<br />

areas are located at the two ends of the plat<strong>for</strong>m and<br />

concourse level.<br />

The station occupant load is 1200 persons.<br />

In Test #1 of Figure B-2.2, the time to clear the plat<strong>for</strong>m is<br />

found to be 2.86 m<strong>in</strong>utes. This meets the requirement of<br />

Cl.2.2.3.3. The sample calculation shows the effect of<br />

discount<strong>in</strong>g one of the escalators from plat<strong>for</strong>m to concourse<br />

<strong>for</strong> the escape route to the right of the station.<br />

In Test #2 of Figure B-2.2, the time to reach a po<strong>in</strong>t outside<br />

Wait<strong>in</strong>g time<br />

at circulation<br />

elements<br />

<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> B-2