2.5.5.2 The fire alarm system shall comply with the requirements of<br />
the SS CP 10 Code of Practice <strong>for</strong> The Installation and<br />
Servic<strong>in</strong>g of Electrical <strong>Fire</strong> Alarm <strong>Systems</strong> except as here<strong>in</strong><br />
modified:<br />
(a) For underground station without <strong>Fire</strong> Command Centre<br />
(FCC), the ma<strong>in</strong> alarm panel shall be located <strong>in</strong> the<br />
firemen’s staircase at ground level. All fire alarm<br />
signals shall also be transmitted to the Passenger<br />
Service Centre (PSC), if provided;<br />
(b) Buffer area, air lock, air plenum, above-ground outdoor<br />
cool<strong>in</strong>g tower enclosure and naturally cross-ventilated<br />
public areas need not be provided with detectors.<br />
(c) Station public areas shall not be provided with alarm<br />
bells and manual call po<strong>in</strong>ts. Ancillary areas of<br />
aboveground light rapid transit (LRT) stations shall not<br />
be provided with alarm bells.<br />
(d) Alarm bells <strong>in</strong> the commercial spaces on the<br />
commercial floor shall only sound if spr<strong>in</strong>klers,<br />
detectors or manual call po<strong>in</strong>ts are activated with<strong>in</strong> the<br />
commercial spaces.<br />
(e) In addition to the alarm bells, sufficient visual<br />
alarm devices e.g. beacon lights shall be provided <strong>in</strong> but<br />
not limited to the follow<strong>in</strong>g plantrooms where the<br />
background noise is excessive:<br />
(i) Environment control system plantroom;<br />
(ii) Tunnel ventilation fan room;<br />
(iii) Underplat<strong>for</strong>m exhaust fan room;<br />
(iv) Smoke extract fan room;<br />
(v) <strong>Civil</strong> Defence generator room; and<br />
(vi) <strong>Civil</strong> Defence cool<strong>in</strong>g tower room.<br />
(f) For fire detection <strong>in</strong> station public areas, l<strong>in</strong>ear heat<br />
detectors of the optic fibre type and optical beam l<strong>in</strong>etype<br />
detectors can be considered <strong>in</strong> the concealed<br />
ceil<strong>in</strong>g spaces and under the ceil<strong>in</strong>gs respectively.<br />
Where l<strong>in</strong>ear heat detectors are used, the coverage shall<br />
be equivalent to the po<strong>in</strong>t-type detectors.<br />
<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 102