2.9.8 MOTORISED TROLLEY<br />
2.9.8.1 Motorised trolley shall be provided at each of the follow<strong>in</strong>g<br />
location:<br />
(a) Station plat<strong>for</strong>m level<br />
(b) Mid tunnel exit staircase more than 380m from a station<br />
(c) Tra<strong>in</strong>way portal<br />
2.9.8.2 Motorised trolley shall be constructed of non-combustible<br />
material and firmly hanged on wall. Accessories (ie. batteries,<br />
battery chargers, ignition key, handle and controller) shall be<br />
housed <strong>in</strong> steel cab<strong>in</strong>et. Signage comply<strong>in</strong>g with SS 508 shall<br />
be provided to read “ACCESSORIES FOR MOTORISED<br />
TROLLEY”. The front part of the cab<strong>in</strong>et must allow the<br />
status of batteries to be easily monitored. The cab<strong>in</strong>et shall be<br />
locked. The key shall be kept <strong>in</strong> a glass-fronted glazed box<br />
alongside the cab<strong>in</strong>et or as part of the cab<strong>in</strong>et. Signage<br />
comply<strong>in</strong>g with SS 508 shall be provided to read “IN CASE<br />
OF EMERGENCY, BREAK GLASS FOR KEYS”. A spare<br />
key shall be kept <strong>in</strong> the PSC.<br />
2.9.8.3 Motorised trolley provided at station plat<strong>for</strong>m level, midtunnel<br />
exit staircase and tra<strong>in</strong>way portal shall have access to all<br />
tra<strong>in</strong>ways. Otherwise, separate motorised trolley shall be<br />
provided <strong>for</strong> each tra<strong>in</strong>way.<br />
2.9.8.4 Motorised trolley provided at station plat<strong>for</strong>m level shall be<br />
with<strong>in</strong> a travel distance of not more than 20m to the end<br />
plat<strong>for</strong>m steps lead<strong>in</strong>g to the trackway.<br />
2.9.8.5 Motorised trolley located <strong>in</strong> mid-tunnel exit staircase shall not<br />
impede the means of escape.<br />
2.9.8.6 Valve regulated lead acid (sealed type) batteries shall be used<br />
<strong>for</strong> the motorised trolley. Two sets of batteries (one spare) shall<br />
be provided <strong>for</strong> each trolley.<br />
2.9.8.7 Ventilation shall be provided to comply with Clause 2.6.2.2(g).<br />
<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 144