(e) Cl.2.3.8.2(c), 2.3.8.4, 2.3.8.7(c), 2.3.8.8(b), 2.3.8.8(f)<br />
& 2.3.8.9(a) <strong>for</strong> Protected Shafts.<br />
2.3.15.3 Materials used <strong>for</strong> the protection of open<strong>in</strong>gs shall comply<br />
with the relevant provisions of Cl. 2.3.9 of the <strong>Standard</strong> <strong>for</strong><br />
protection of open<strong>in</strong>gs.<br />
2.3.15.4 Exit staircases shall be constructed of non-combustible<br />
materials to comply with the provisions of Cl. 2.3.10.1.<br />
2.3.15.5 Materials used <strong>for</strong> the construction of raised floors shall<br />
comply with the provisions of Cl. 2.3.11.7(a) and<br />
Cl. 2.3.11.7(e).<br />
2.3.15.6 Materials used <strong>for</strong> construction of ceil<strong>in</strong>g supports shall<br />
comply with the provisions of Cl. 2.3.11.8(a).<br />
2.3.15.7 Materials used <strong>for</strong> fire stopp<strong>in</strong>g shall comply with the<br />
relevant provisions of Cl. 2.3.12.2 and 2.3.12.3.<br />
2.3.15.8 Materials used <strong>for</strong> roof construction shall comply with the<br />
provisions of Cl. 2.3.14.1.<br />
2.3.15.9 Internal non-load bear<strong>in</strong>g walls, partitions, cladd<strong>in</strong>gs/wall<br />
panels, false ceil<strong>in</strong>g, balustrades and rail<strong>in</strong>gs <strong>in</strong> stations,<br />
<strong>in</strong>clud<strong>in</strong>g the materials <strong>for</strong> surface f<strong>in</strong>ishes, shall be<br />
constructed of non-combustible materials.<br />
Exception: Wall f<strong>in</strong>ishes <strong>in</strong> the <strong>for</strong>m of th<strong>in</strong> sheets of not<br />
more than 1.0 mm thickness mounted on noncombustible<br />
substrate <strong>in</strong> commercial space<br />
where spr<strong>in</strong>kler protection is provided.<br />
2.3.15.10 Composite panels and sandwich panels which has noncombustible<br />
cover<strong>in</strong>g but consist of plastic or combustible<br />
core are prohibited.<br />
2.3.15.11 PVC pipes are prohibited <strong>in</strong> underground stations.<br />
Exception 1: Encased PVC pipes <strong>in</strong> concrete.<br />
Exception 2: PVC pipe sleeves <strong>in</strong> structure.<br />
Exception 3: Condensate dra<strong>in</strong> pipes <strong>for</strong> air-condition<strong>in</strong>g<br />
units.<br />
<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 76