vi) The outer radius <strong>for</strong> turn<strong>in</strong>g of access and fire<br />

eng<strong>in</strong>e access road shall comply with the<br />

requirements as shown <strong>in</strong> Diagram 2.4.2.4(b)(vi).<br />

vii) Overhead clearance of accessway and fire eng<strong>in</strong>e<br />

access road shall be at least 4.5m <strong>for</strong> passage of<br />

fire fight<strong>in</strong>g appliances.<br />

viii) Public roads can serve as accessway provided the<br />

location of such public roads is <strong>in</strong> compliance<br />

with the requirements of distance from access<br />

open<strong>in</strong>gs.<br />

ix) Accessway and fire eng<strong>in</strong>e access road shall be<br />

kept clear of obstructions and other parts of the<br />

station, plants, trees or other fixtures shall not<br />

obstruct the path between the accessway and<br />

access open<strong>in</strong>gs.<br />

(c) i) All corners of accessway shall be marked.<br />

ii) Mark<strong>in</strong>g of corners shall be <strong>in</strong> contrast<strong>in</strong>g colour<br />

to the ground surfaces or f<strong>in</strong>ishes.<br />

iii) Accessway provided on turfed area must be<br />

marked with contrast<strong>in</strong>g object (preferably<br />

reflective) that is visible at night.<br />

The mark<strong>in</strong>gs are to be at <strong>in</strong>tervals not more than<br />

3m apart and shall be provided on both sides of<br />

the accessway.<br />

iv) Sign post display<strong>in</strong>g the word<strong>in</strong>gs '<strong>Fire</strong> Eng<strong>in</strong>e<br />

Access - Keep Clear' shall be provided at the<br />

entrance of the accessway. Size of word<strong>in</strong>gs shall<br />

not be less than 50mm.<br />

2.4.3 ACCESS TO STATIONS WITH BREECHING INLETS<br />

Station fitted with ris<strong>in</strong>g ma<strong>in</strong>s and automatic spr<strong>in</strong>kler system<br />

shall have fire eng<strong>in</strong>e access roads <strong>for</strong> pump<strong>in</strong>g appliances<br />

with<strong>in</strong> 18m of the breech<strong>in</strong>g <strong>in</strong>lets. The breech<strong>in</strong>g <strong>in</strong>lets shall<br />

be visible from the fire eng<strong>in</strong>e access roads.<br />

Overhead<br />

clearance<br />

Public road<br />

Obstruction<br />

Mark<strong>in</strong>g of<br />

fire eng<strong>in</strong>e<br />

accessway<br />

Access to<br />

stations with<br />

breech<strong>in</strong>g<br />

<strong>in</strong>lets<br />

<strong>Standard</strong> <strong>for</strong> <strong>Fire</strong> <strong>Safety</strong> <strong>in</strong> <strong>Rapid</strong> <strong>Transit</strong> <strong>Systems</strong> 87

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!