PROTECTION THICKNESS<br />

Thickness recommendations given in "Fire<br />

Protection of Structural <strong>Steel</strong> in Building" have<br />

normally been derived from fire tests on orthodox<br />

H or I rolled sections. For other sections the<br />

recommended thickness for a given section<br />

factor and fire rating should be modified as<br />

follows:<br />

Fire resistance 1287<br />

CASTELLATED SECTIONS HOLLOW SECTIONS<br />

The thickness of fire protection material on a For intumescent materials applied to hollow<br />

castellated section should be 20% greater than that sections the manufacturers should have carried<br />

required for the section from which it was cut. out separate tests and appraisal