Typical recommendations for fire resistance of Web Infilled Columns, taken from the <strong>Steel</strong> Construction<br />

Institute publication, are given in Table 1<br />

Table I<br />

Fire Resistance 60 minutes<br />

Column Grade $275<br />

Section Size<br />

Moment Load Compressive Capacity (kN) at effective<br />

Capacity (kNm) Ratio1 lengths used for normal design<br />

M M<br />

203 x 203 x 46 40.3 22.9<br />

203 x 203 x 52 47.0 25.4<br />

203 x 203 x 60 56.7 29.0<br />

203 x 203 x 71 69.9 34.6<br />

2500mm 3000mm 3500mm 4000mm 4500mm<br />

0.57 744 682 616 551 488<br />

0.54 803 738 669 600 533<br />

0.52 882 881 735 659 586<br />

0.49 974 899 820 740 662<br />

1Load Ratio is defined in B55950 Part 8 as the ratio of the load at the fire limit state to the cold<br />

capacity of the section.<br />

M = the moment capacity in fire conditions for bending about the x - x axis.<br />

M = the moment capacity in fire conditions for bending about they - y axis.<br />

Fire resistance 1301