<strong>Steel</strong> <strong>Designers</strong>' <strong>Manual</strong> - 6th Edition (2003)<br />

a a<br />

a<br />

a<br />

overlap<br />

(a) (b)<br />

cover width of decking<br />

C b b_______<br />

Fig. 21.16 Potential failure planes through slab in longitudinal shear<br />

the decking is continuous over the beams, as in Fig. 21.3(a), or rigidly attached by<br />

shear-connectors, there is no test evidence of the splitting mode of failure. It is<br />

assumed, therefore, that the deck is able to provide an important role as transverse<br />

reinforcement. The term Arfy may be enhanced to include the contribution of the<br />

decking, although it is necessary to ensure that the ends of the deck (butt joints)<br />

are properly welded by shear-connectors. In this case, the anchorage provided by<br />

each weld may be taken as 4f tspy, where f is the stud diameter, ts is the sheet thickness,<br />

and py is the strength of the sheet steel. Dividing by the stud spacing gives the<br />

equivalent shear resistance per unit length provided by the decking.<br />

Where the decking is laid parallel to the beams, longitudinal shear failure can<br />

occur through the sheet-to-sheet overlap close to the line of studs. Failure is assessed<br />

assuming the shear force transferred diminishes linearly across the slab to zero at<br />

a distance of Bc/2. Therefore, the effective shear force that is transferred across the<br />

longitudinal overlaps is (1 – cover width of decking/effective breadth) ¥ shear force.<br />

The shear resistance at overlaps excludes the effect of the decking.<br />

To prevent splitting of the slab at edge beams, the distance between the line of<br />

shear-connectors and the edge of the slab should not be less than 100 mm. When<br />

this distance is between 100 mm and 300 mm, additional reinforcement in the<br />

form of U bars located below the head of the shear-connectors is to be provided. 12<br />

No additional reinforcement (other than that for transverse reinforcement) need<br />

be provided where the edge of the slab is more than 300 mm from the shearconnectors.<br />

21.7.7 Interaction of shear and moment in composite beams<br />

Basic design 623<br />

Vertical shear can cause a reduction in the plastic moment resistance of a composite<br />

beam where high moment and shear co-exist at the same position along the beam