6. Air tanks installed on the right-<strong>of</strong>-way <strong>of</strong> railroads (under federal or other commonwealth agency jurisdiction) used<br />

directly in the operation <strong>of</strong> switches <strong>and</strong> signals.<br />

7. <strong>Boiler</strong>s located in single-family dwellings or multi-unit dwellings with four or fewer units.<br />

ObJeCtS SUbJeCt tO rUleS FOr FIelD InSpeCtIOn<br />

Same as OBJECTS SUBJECT TO RULES FOR CONSTRUCTION AND STAMPING.<br />

InSpeCtIOnS reQUIreD<br />

Item Field Inspection<br />

Power boilers, internal <strong>and</strong> external 1 Year<br />

Miniature boilers 1 Year<br />

Low-pressure steam vapor, hot-water heating <strong>and</strong> hot-water supply boilers 2 Years<br />

Unfired pressure vessels<br />

Nuclear vessels: Type <strong>and</strong> frequency <strong>of</strong> inspection will be determined by<br />

the chief inspector.<br />

3 Years<br />

1. Power boiler internal inspections may be extended to 24 months if:<br />

a. <strong>Boiler</strong> water treatment is continuously under direct supervision <strong>of</strong> trained personnel.<br />

b. Recordkeeping shows date <strong>and</strong> time boiler out <strong>of</strong> service <strong>and</strong> why, <strong>and</strong> water condition based on daily sample<br />

analysis (illustrating elements which may cause corrosion).<br />

c. External inspections are performed by a commonwealth-commissioned inspector.<br />

d. <strong>Boiler</strong> is operated under direct supervision <strong>of</strong> qualified persons, <strong>and</strong> inspection records demonstrate no significant<br />

scaling, corrosion, or overheating.<br />

2. Process boiler internal inspections may be extended to 60 months if meeting the above criteria plus being in continuous<br />

operation <strong>and</strong> fully attended.<br />

InSUranCe InSpeCtIOn reQUIrementS<br />

1. Inspections made by inspectors <strong>of</strong> authorized insurance companies <strong>and</strong> companies operating vessels in Pennsylvania<br />

who have been commissioned by the section are accepted in lieu <strong>of</strong> inspections made by a boiler section inspector.<br />

2. Any person, firm, partnership or corporation operating boilers or pressure vessels in the commonwealth may seek approval<br />

<strong>and</strong> registration as an owner/user inspection agency through the Department <strong>of</strong> Labor <strong>and</strong> Industry.<br />

CertIFICate OF InSpeCtIOn<br />

Certificate <strong>of</strong> Operation, when approved, is issued by the boiler section for boilers <strong>and</strong> pressure vessels upon payment <strong>of</strong> the following<br />

fees:<br />

1. <strong>Boiler</strong>s, for a period <strong>of</strong> 12–24 months, by law .......................................................................................................... $22.00 per year<br />

2. Pressure vessels, for a period <strong>of</strong> 36 months ............................................................................................................. $22.00 per year<br />

State FeeS<br />

1. Power, high-temperature, high-pressure <strong>and</strong> miniature boilers — internal:<br />

a. 50 square feet heating surface <strong>and</strong> less ............................................................................................................................... $22.00<br />

b. More than 50 square feet heating surface <strong>and</strong> less than 4,000 square feet ................................................................$36.00<br />

c. More than 4,000 square feet heating surface <strong>and</strong> less than 10,000 square feet ........................................................$51.00<br />

d. More than 10,000 square feet heating surface .................................................................................................................. $58.00<br />

e. Miniature boilers ...................................................................................................................................................................... $15.00<br />

2. Power, high-temperature, high-pressure, <strong>and</strong> miniature boilers – external:<br />

a. 50 square feet heating surface <strong>and</strong> less ............................................................................................................................... $15.00<br />

b. More than 50 square feet heating surface <strong>and</strong> less than 4,000 square feet ................................................................$22.00<br />