92<br />

ObJeCtS SUbJeCt tO rUleS FOr COnStrUCtIOn anD StampInG<br />

1. All boilers within the scope <strong>of</strong> Section I <strong>of</strong> the ASME Code.<br />

2. All low-pressure boilers <strong>and</strong> lined water heaters within the scope <strong>of</strong> Section IV <strong>of</strong> the ASME Code.<br />

3. All pressure vessels within the scope <strong>of</strong> Section VIII <strong>of</strong> the ASME Code, except the following:<br />

a. Pressure vessels that meet the requirements <strong>of</strong> US Department <strong>of</strong> Transportation for the shipment <strong>of</strong> liquids or<br />

gases under pressure;<br />

b. Air tanks, integral to brake systems, located on vehicles operating under the rules <strong>of</strong> other state authorities <strong>and</strong><br />

used for carrying passengers or freight, or used for storage <strong>of</strong> compressed air only.<br />

ObJeCtS SUbJeCt tO rUleS FOr FIelD InSpeCtIOn<br />

Mechanical Unit jurisdiction, same as OBJECTS SUBJECT TO RULES FOR CONSTRUCTION AND STAMPING, except:<br />

1. <strong>Boiler</strong>s <strong>and</strong> pressure vessels under federal control.<br />

2. Pressure vessels operating under the laws <strong>of</strong> other states.<br />

3. Unfired pressure vessels having an inside diameter not exceeding 6 inches.<br />

4. Unfired pressure vessels containing cold water under pressure, including those containing air, the compression <strong>of</strong> which<br />

serves only as a cushion.<br />

5. Hot-water supply boilers which are directly fired with oil, gas, or electricity, or pressure vessels containing water heated<br />

by steam or by any other means, if none <strong>of</strong> the following limitations is exceeded:<br />

a. A heat input <strong>of</strong> 199,999 BTU per hour;<br />

b. A water temperature <strong>of</strong> 210°F;<br />

c. A water capacity <strong>of</strong> 120 gallons.<br />

6. Unfired pressure vessels not exceeding 5 cubic feet in volume <strong>and</strong> 15 psig.<br />

7. An unfired pressure vessel which may be classified as a pressure container (an integral part or component <strong>of</strong> a rotating<br />

or reciprocating mechanical device such as a pump, compressor, turbine, generator, engine, or hydraulic or pneumatic<br />

cylinder in which the primary design considerations <strong>and</strong>/or stresses are derived from the functional requirements <strong>of</strong> the<br />

device).<br />

8. Unfired pressure vessels used for the storage <strong>of</strong> compressed air only.<br />

9. A hot-water heater constructed <strong>of</strong> continuous coil, used only to produce steam vapor to clean things such as machinery,<br />

equipment <strong>and</strong> buildings, if:<br />

a. Tubing or pipe size does not exceed 3/4-inch in diameter (drums <strong>and</strong> headers not attached);<br />

b. Nominal water-containing capacity does not exceed 6 gallons;<br />

c. Water temperatures do not exceed 350°F;<br />

d. Steam is not generated within the coil.<br />

10. Pressure vessels <strong>and</strong> piping containing liquid petroleum gas <strong>and</strong> liquid natural gas.<br />

11. A boiler or heater for a pool, if:<br />

a. <strong>The</strong> supply or return line has no stop valve installed;<br />

b. It is impossible for the unit to build pressure in excess <strong>of</strong> 15 psig.<br />

12. <strong>Boiler</strong>s <strong>and</strong> pressure vessels installed in a single family residence unless the boiler or pressure vessel is a:<br />

a. Hot water supply boiler;<br />

b. Hot water supply tank that has a storage capacity which exceeds 120 gallons;<br />

c. Low pressure heating boiler;<br />

d. Power boiler;<br />

e. Pressure vessel that:<br />

i. Operates at pressures that exceed 15 psig;<br />

ii. Has a storage capacity <strong>of</strong> five cubic feet or more by volume.<br />