Laws, Rules and Regulations - The National Board of Boiler and ...
Laws, Rules and Regulations - The National Board of Boiler and ...
Laws, Rules and Regulations - The National Board of Boiler and ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
220<br />
mUnICIpal Department<br />
Mike Centineo, Director<br />
Rudy Hardouin, Chief Mechanical Inspector<br />
Department <strong>of</strong> Safety <strong>and</strong> Permits<br />
Mechanical Inspection Bureau<br />
1300 Perdido Street, Room 7E05<br />
New Orleans, LA 70112<br />
Telephone — 504.658.7165<br />
Fax — 504.565.7211<br />
neW OrleanS, lOUISIana<br />
empOWerment<br />
Chief boiler inspector empowered to make, alter, amend, <strong>and</strong> interpret rules <strong>and</strong> regulations.<br />
<strong>Boiler</strong> <strong>Board</strong>: No.<br />
Date OF laW paSSaGe: 1929<br />
Date <strong>of</strong> latest amendment to law: January 2004.<br />
Date rules <strong>and</strong> regulations implemented: 2004.<br />
Date <strong>of</strong> latest amendment to rules <strong>and</strong> regulations: January 2004.<br />
City ordinance: City <strong>of</strong> New Orleans amendment to the 2000 ICC Mechanical Code.<br />
rUleS FOr COnStrUCtIOn anD StampInG<br />
Construction:<br />
1. ASME Code (2001 Edition, 2002 Addendum), Sections I, II, III, IV, V, VI, VII, VIII (Divisions 1, 2), IX, X, XI.<br />
2. Code rules updated annually.<br />
3. Manufacturer’s Data Reports on ASME forms must be filed with the department before installation.<br />
4. <strong>National</strong> <strong>Board</strong> Inspection Code (1998 Edition, 2000 Addendum).<br />
5. <strong>National</strong> <strong>Board</strong> registration required for boilers <strong>and</strong> pressure vessels.<br />
6. Special design or construction must be approved by the department.<br />
Stamping:<br />
Where appropriate, the following <strong>National</strong> <strong>Board</strong> stamps or ASME Code symbol stamps are required:<br />
1. <strong>National</strong> <strong>Board</strong>: NR, R, VR.<br />
2. ASME Code: all.<br />
ObJeCtS SUbJeCt tO rUleS FOr COnStrUCtIOn anD StampInG<br />
All steam hot-water heating <strong>and</strong> hot-water supply boilers, <strong>and</strong> unfired pressure vessels, except: boilers <strong>and</strong> unfired pressure vessels<br />
in marine or railroad service under the inspection regulations <strong>of</strong> the federal government.<br />
ObJeCtS SUbJeCt tO rUleS FOr FIelD InSpeCtIOn<br />
Same as OBJECTS SUBJECT TO RULES FOR CONSTRUCTION AND STAMPING, except the following:<br />
1. Steam boilers operating at 15 psi or less <strong>and</strong> hot-water boilers, provided they are built in accordance with ASME Code<br />
<strong>and</strong> located in private residences or dwellings <strong>of</strong> four families or fewer.<br />
2. Unfired pressure vessels built in accordance with ASME Code <strong>and</strong> do not exceed:<br />
a. Volume <strong>of</strong> 5 cubic feet;<br />
b. Design pressure <strong>of</strong> 250 psi.<br />
IMPORTANT NOTICE: Every effort has been made to make<br />
this synopsis as accurate <strong>and</strong> complete as possible. However,<br />
jurisdictional laws, regulations <strong>and</strong> rules are subject to change<br />
without notice. As a result, the information contained herein is<br />
neither guaranteed nor warranted. User is advised to consult<br />
the jurisdiction’s chief inspector before reaching any decision that<br />
may have critical impact or significant financial consequences.<br />
<strong>The</strong> <strong>National</strong> <strong>Board</strong> assumes no responsibility for information<br />
posted on external Web sites.<br />
2013 <strong>National</strong> <strong>Board</strong> Synopsis <strong>of</strong> <strong>Boiler</strong> <strong>and</strong> Pressure Vessel <strong>Laws</strong>, <strong>Rules</strong> <strong>and</strong> <strong>Regulations</strong>