Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

8<br />

ObJeCtS SUbJeCt tO rUleS FOr COnStrUCtIOn anD StampInG<br />

All boilers, lined hot water heaters <strong>and</strong> pressure vessels, except the following:<br />

1. <strong>Boiler</strong>s, lined hot water heaters <strong>and</strong> pressure vessels regulated by the US government.<br />

2. <strong>Boiler</strong>s, lined hot water heaters <strong>and</strong> pressure vessels located in private residences, or apartment complexes <strong>of</strong> not more<br />

than six units.<br />

3. <strong>Boiler</strong>s, lined hot water heaters <strong>and</strong> pressure vessels operated on Indian reservations.<br />

ObJeCtS SUbJeCt tO rUleS FOr FIelD InSpeCtIOn<br />

Same as OBJECTS SUBJECT TO RULES FOR CONSTRUCTION AND STAMPING.<br />

InSpeCtIOnS reQUIreD<br />

1. Power <strong>and</strong> high temperature water boilers:<br />

a. An annual internal certificate inspection <strong>and</strong> an external inspection while under operating conditions;<br />

b. An internal inspection if the inspector determines from an external inspection that there is danger to public or<br />

worker safety.<br />

c. A triennial (36-month) internal inspection <strong>and</strong> annual external inspection when fully attended by quilified<br />

attendants.<br />

2. Direct fired jacketed steam kettles: inspection every two years.<br />

3. Heating or process boilers, not exceeding 15 psi (steam or vapor):<br />

a. A certificate inspection every two years;<br />

b. An internal inspection where construction permits.<br />

4. Hot-water heating boilers <strong>and</strong> lined hot-water heaters operating at pressures not exceeding 160 psi <strong>and</strong> temperatures<br />

not exceeding 250°F: An initial certificate inspection with no further inspections required (may be an external<br />

inspection).<br />

5. Lined hot-water heaters are exempted when none <strong>of</strong> the following limitations are exceeded:<br />

a. Heat input <strong>of</strong> 200,000 BTU per hour;<br />

b. Water temperature <strong>of</strong> 210°F;<br />

c. Nominal water-containing capacity <strong>of</strong> 120 gallons.<br />

<strong>The</strong> Certificate <strong>of</strong> Inspection may be made 30 days prior to the certificate due date, but in all cases shall not be more than 30 days<br />

after such date.<br />

InSUranCe InSpeCtIOn reQUIrementS<br />

1. Insurance companies are required to inspect to the Arizona <strong>Boiler</strong> <strong>Rules</strong> (Title 20, Chapter 5, Article 4); ASME Codes I, II,<br />

IV, V, Vlll (Div, 1, 2, 3), lX, B31.1 <strong>and</strong> requirements <strong>of</strong> the <strong>National</strong> <strong>Board</strong> Inspection Code.<br />

2. Inspections made by inspectors employed by insurance companies <strong>and</strong> issued a special inspection certificate by the chief<br />

boiler inspector are accepted in lieu <strong>of</strong> inspections made by a state inspector.<br />

3. Reports <strong>of</strong> certificate inspections must be filed with the division on forms equivalent to the NB-6 form <strong>of</strong> the <strong>National</strong><br />

<strong>Board</strong> Inspection Code within 60 days after inspection.<br />

4. Reports <strong>of</strong> external inspections other than certificate inspections are not required unless there are code violations or<br />

unsafe conditions.<br />

5. Written, canceled, not renewed or suspended because <strong>of</strong> unsafe conditions: All insurance companies shall notify the division,<br />

on <strong>National</strong> <strong>Board</strong> forms, within 30 days <strong>of</strong> all boiler risks.<br />

6. All insurance companies shall immediately notify the division <strong>of</strong> any unsafe boiler which they refuse to insure, <strong>and</strong><br />

submit a report <strong>of</strong> defects.<br />

2013 <strong>National</strong> <strong>Board</strong> Synopsis <strong>of</strong> <strong>Boiler</strong> <strong>and</strong> Pressure Vessel <strong>Laws</strong>, <strong>Rules</strong> <strong>and</strong> <strong>Regulations</strong>