169<br />

1. <strong>National</strong> <strong>Board</strong>: R (accepted).<br />

2. ASME Code: all.<br />

Special stamping: CRN.<br />

ObJeCtS SUbJeCt tO rUleS FOr COnStrUCtIOn anD StampInG<br />

All boilers, pressure vessels, pressure piping systems, fittings, <strong>and</strong> plant <strong>and</strong> refrigeration equipment, except:<br />

1. <strong>Boiler</strong>s used in private residences or apartments <strong>of</strong> fewer than five units<br />

2. Power boilers not exceeding 2 m2 .<br />

3. Hot water boilers not exceeding 3 m2 .<br />

4. Hot water boilers that have no valves or other obstruction to prevent circulation <strong>of</strong> fluid between the boiler <strong>and</strong> an<br />

expansion tank that is fully vented to the atmosphere.<br />

5. Pressure vessels not equipped with a heating element that is constructed for the storage <strong>of</strong> water at a temperature <strong>of</strong><br />

65ºC or less <strong>and</strong> a pressure <strong>of</strong> 1 720 kPa or less or has a diameter <strong>of</strong> 610 mm or less.<br />

6. Pressure vessels used for hydraulic purposes having an operating temperature <strong>of</strong> less than 82ºC, if the primary design<br />

considerations are mechanical in nature <strong>and</strong> stresses are derived from the functional requirements <strong>of</strong> the device rather<br />

than fluid pressure.<br />

7. Refrigeration plants with a capacity not exceeding 5 kW.<br />

8. Cushion tanks with diameters <strong>of</strong> 610 mm or less constructed to operate at a working pressure not exceeding 207 kPa.<br />

9. Piping systems not exceeding 103 kPa.<br />

Miscellaneous<br />

In addition to power boilers above 10 m2 in #6 the following require licensed operators:<br />

1. Low pressure steam boilers exceeding 30 m 2 .<br />

2. Hot water heating boilers exceeding 150 m 2 .<br />

3. Refrigeration plants with refrigerant groups A1, A2 or B1, as defined in CSA B52, exceeding a total plant capacity <strong>of</strong><br />

200 kW prime mover nameplate rating.<br />

4. Refrigeration plant with refrigerant groups A3, B2 or B3, as defined in CSA B52, exceeding a total plant capacity <strong>of</strong><br />

50 kW prime mover nameplate rating.<br />

See Power Engineers, <strong>Boiler</strong>, Pressure Vessel, <strong>and</strong> Refrigeration Safety Regulation, Section 3, Application, for minimum capacities <strong>and</strong><br />

other details.<br />

ObJeCtS SUbJeCt tO rUleS FOr FIelD InSpeCtIOn<br />

Same as OBJECTS SUBJECT TO RULES FOR CONSTRUCTION AND STAMPING.<br />

InSpeCtIOnS reQUIreD (INSPECTION FREQUENCY BASED ON A RISK ASSESSMENT PROGRAM)<br />

1. High-pressure <strong>and</strong> low-pressure steam boilers.<br />

2. Hot-water heating boilers.<br />

3. Pressure vessels.<br />

4. Refrigeration Plants.<br />

InSUranCe InSpeCtIOn reQUIrementS<br />

Inspections made by inspectors employed by insurance companies are not accepted in lieu <strong>of</strong> inspections made by a BCSA <strong>Boiler</strong><br />

Safety Officer.<br />

CertIFICate OF InSpeCtIOn<br />

Certificate <strong>of</strong> Inspection, valid until next inspection, is issued by the BCSA.<br />