156<br />

3. Steam boilers used exclusively for heating purposes carrying a pressure <strong>of</strong> not more than 15 psig <strong>and</strong> which are located<br />

in private residences or in apartment houses <strong>of</strong> fewer than six families.<br />

4. Hot-water heating boilers with a pressure <strong>of</strong> not more than 30 psi located in private residences or apartment houses <strong>of</strong><br />

fewer than six families.<br />

5. Approved pressure vessels (hot-water heaters, hot-water storage tanks, hot-water supply boilers, <strong>and</strong> hot-water heating<br />

boilers), with approved safety devices including pressure relief valve, with nominal water-containing capacity <strong>of</strong><br />

120 gallons or less having a heat input <strong>of</strong> 200,000 BTU per hour or less, used for hot-water supply at a pressure <strong>of</strong><br />

160 psi or less, <strong>and</strong> at temperatures <strong>of</strong> 210°F or less provided, however, that such pressure vessels are not installed in<br />

schools, childcare centers, public <strong>and</strong> private hospitals, nursing <strong>and</strong> boarding homes, churches, public buildings owned or<br />

leased <strong>and</strong> maintained by the state or any political subdivision there<strong>of</strong>, <strong>and</strong> assembly halls.<br />

6. Unfired pressure vessels containing only water under pressure for domestic supply purposes (including those containing<br />

air, the compression <strong>of</strong> which serves only as a cushion or airlift pumping system), when located in private residences or<br />

in apartment houses <strong>of</strong> fewer than six families, or in public water systems as defined in RCW 70.119.020.<br />

7. Unfired pressure vessels containing liquified petroleum gases.<br />

InSpeCtIOnS reQUIreD<br />

Item Internal External<br />

Power boilers 1 Year 1 Year*<br />

Organic vapor boilers 2 Years 1 Year*<br />

Low-pressure heating boilers 2 Years 2 Years**<br />

One biennial internal inspection <strong>of</strong> low-water fuel cut<strong>of</strong>f.<br />

Hot-water heaters — 2 Years<br />

Unfired pressure vessels 2 Years*** 2 Years<br />

*One inspection while under pressure <strong>and</strong> one not under pressure.<br />

**Under pressure.<br />

***When subject to corrosion.<br />

InSUranCe InSpeCtIOn reQUIrementS<br />

1. All insurance companies shall notify the chief inspector within 30 days <strong>of</strong> all boiler <strong>and</strong>/or unfired pressure vessel risks<br />

written, canceled, not renewed, or suspended because <strong>of</strong> unsafe conditions. Special inspectors shall perform all inservice<br />

inspections <strong>of</strong> boilers <strong>and</strong> unfired pressure vessels insured by their employer. Inspections made by inspectors employed<br />

by insurance companies <strong>and</strong> commissioned by the department are accepted in lieu <strong>of</strong> inspections by a department<br />

inspector.<br />

2. Reports <strong>of</strong> internal <strong>and</strong> external inspections must be filed with the department on approved forms within 30 days after<br />

inspection.<br />

CertIFICate OF InSpeCtIOn<br />

1. Certificate <strong>of</strong> Inspection, valid for not more than 14 months for power boilers <strong>and</strong> for not more than 26 months for lowpressure<br />

boilers <strong>and</strong> pressure vessels, will be issued by the department upon payment <strong>of</strong> a fee to the department.<br />

2. No Certificate <strong>of</strong> Inspection issued for an insured boiler or pressure vessel shall be valid after the boiler or pressure vessel<br />

ceases to be insured by a duly authorized insurance company.<br />

State FeeS<br />

1. Heating boilers (internal inspection):<br />

a. Cast iron, all sizes ..................................................................................................................................................................... $36.30<br />

b. All other boilers less than 500 square feet ........................................................................................................................ $36.30<br />

c. 500 square feet to 2,500 square feet ................................................................................................................................... $72.40<br />

d. Each additional 2,500 square feet <strong>of</strong> total heating surface, or any portion there<strong>of</strong> ..................................................$29.00<br />

2. Heating boilers (external inspection):<br />

a. Cast iron, all sizes ..................................................................................................................................................................... $29.00<br />

b. All other boilers less than 500 square feet ........................................................................................................................ $29.00<br />

2013 <strong>National</strong> <strong>Board</strong> Synopsis <strong>of</strong> <strong>Boiler</strong> <strong>and</strong> Pressure Vessel <strong>Laws</strong>, <strong>Rules</strong> <strong>and</strong> <strong>Regulations</strong>