Model <strong>3G3HV</strong>-<br />

200-V class 400-V class<br />

Max. motor<br />

capacity<br />

Rated current<br />

(A)<br />

(Default-set)<br />

Model<br />

<strong>3G3HV</strong>-<br />

Max. motor<br />

capacity<br />

Rated current<br />

(A)<br />

(Default-set)<br />

--- 0.4 kW 1.9 --- 0.4 kW 1.0<br />

--- 0.75 kW 3.3 --- 0.75 kW 1.6<br />

--- 1.5 kW 6.2 --- 1.5 kW 3.1<br />

--- 2.2 kW 8.5 --- 2.2 kW 4.2<br />

A2037 3.7 kW 14.0 A4037 3.7 kW 7.0<br />

A2055 5.5 kW 19.6 A4055 5.5 kW 9.8<br />

A2075 7.5 kW 26.6 A4075 7.5 kW 13.3<br />

A2110 11 kW 39.7 A4110 11 kW 19.9<br />

A2150 15 kW 53.0 A4150 15 kW 36.5<br />

B2185 18.5 kW 65.8 B4185 18.5 kW 32.9<br />

B2220 22 kW 77.2 B4220 22 kW 38.6<br />

B2300 30 kW 105.0 B4300 30 kW 52.3<br />

B2370 37 kW 131.0 B4370 37 kW 65.6<br />

B2450 45 kW 156.0 B4450 45 kW 79.7<br />

B2550 55 kW 190.0 B4550 55 kW 95.0<br />

B2750 75 kW 260.0 B4750 75 kW 130.0<br />

--- --- --- B411K 110 kW 190.0<br />

--- --- --- B416K 160 kW 270.0<br />

--- --- --- B418K 185 kW 310.0<br />

--- --- --- B422K 220 kW 370.0<br />

--- --- --- B430K 300 kW 500.0<br />

n033<br />

Setting range<br />

Electronic Thermal Protection Function Selection<br />

0, 1, 2, 3, and<br />

4<br />

Unit --- Default setting<br />

1<br />

Set Values<br />

Set<br />

Description<br />

value<br />

0 No protection.<br />

1 For standard motors with standard ratings (with a time constant of 8 min).<br />

2 For standard motors with short-time ratings (with a time constant of 5 min).<br />

3 For dedicated motors with standard ratings (with a time constant of 8 min).<br />

4 For dedicated motors with short-time ratings (with a time constant of 5 min).<br />

Note If more than one motor is operated with a single Inverter, install a thermal relay between<br />

the Inverter and the motor and set n033 to 0.<br />

n034<br />

Selection of Stop Method for when Radiation Fin<br />

Overheats<br />

Setting range 0, 1, 2, and 3 Unit --- Default setting<br />

• The Inverter will detect the heat sink overheat warning OH1 when the<br />

temperature of the heat sink reaches approximately 90°C. Select a<br />

method to interrupt the operation of the Inverter with n034.<br />