Function<br />
Frequency<br />
reference<br />
function<br />
selection<br />
No.<br />
n040<br />
n041<br />
n042<br />
n043<br />
n044<br />
n045<br />
n046<br />
Name<br />
Sequential<br />
output function<br />
selection<br />
Multi-function<br />
contact<br />
output 1<br />
(MA-MB-<br />
MC)<br />
Multi-function<br />
contact<br />
output 2<br />
(M1-M2)<br />
Analog frequency<br />
reference<br />
voltage/current<br />
selection<br />
FI input level<br />
selection<br />
Analog frequency<br />
reference<br />
sample<br />
hold selection<br />
Processing<br />
selection<br />
when analog<br />
frequency<br />
reference<br />
is<br />
lost<br />
Frequency<br />
reference<br />
gain<br />
Description<br />
0: Error (ON: Error)<br />
1: Running<br />
2: Frequency agreement<br />
3: Optional frequency agreement<br />
4: Optional frequency detection (ON:<br />
Output frequency n073)<br />
5: Optional frequency detection (ON:<br />
Output frequency n073)<br />
6: Overtorque (ON: Detected)<br />
7: Overtorque (OFF: Detected)<br />
8: Baseblock<br />
9: Operation mode (ON: Digital Operator/Frequency<br />
reference)<br />
10: Inverter ready<br />
11: Timer function output (Set with n077<br />
and n078)<br />
12: Error retrying<br />
13: Inverter/Motor overload warning<br />
14: Frequency reference loss (ON: Frequency<br />
reference has dropped by<br />
90% or more within 0.4 s)<br />
15: Not used<br />
16: PID feedback loss (Detecting method<br />
can be set with n093 and n094)<br />
17: Heating heat sink (ON: OH1)<br />
Setting<br />
range<br />
0 to 17<br />
[0]<br />
Same as n040 0 to 17<br />
0: The FV terminal can be used for the<br />
analog frequency reference within a<br />
voltage range from 0 to 10 VDC.<br />
1: The FI terminal can be used for the<br />
analog frequency reference. Set the<br />
input level with n043.<br />
0: Voltage input within a range from 0 to<br />
10 V. Be sure to cut jumper wire J1.<br />
1: Current input within a range from 4 to<br />
20 mA.<br />
0: Frequency reference on hold is not<br />
saved.<br />
1: Frequency reference on hold is saved<br />
by n025<br />
0: Inhibits Inverter from processing analog<br />
frequency reference loss.<br />
1: Permits Inverter to process analog frequency<br />
reference loss.<br />
Set analog frequency reference input gain.<br />
Set input frequency at 10 V or 20 mA with<br />
1% units based on max. frequency set<br />
with n012 as 100%.<br />
[1]<br />
0, 1<br />
[0]<br />
0, 1<br />
[1]<br />
0, 1<br />
[0]<br />
0, 1<br />
[0]<br />
0 to<br />
200<br />
[100]<br />
User<br />
setting