n003<br />
Setting range 150.0 to 255.0<br />
(510.0)<br />
Input Voltage Selection<br />
Set the stop mode of the Inverter with n004.<br />
Unit V Default setting<br />
200.0 (400.0)<br />
n004<br />
Interruption Mode Selection<br />
Setting range 0 to 3 Unit --- Default setting<br />
0<br />
Set Values<br />
Set<br />
Description<br />
value<br />
0 Deceleration stop<br />
1 Free running stop<br />
2 Free running stop 1 with timer. The run command during acceleration time 1 or 2 will be<br />
ignored.<br />
3 Free running stop 2 with timer. The constant run command is valid. The motor will start<br />
running after deceleration time 1 or 2 passes.<br />
Set n008 so that the STOP/RESET Key will function properly.<br />
n008<br />
Stop Key Function Selection<br />
Setting range 0, 1 Unit --- Default setting<br />
1<br />
Set Values<br />
Set<br />
Description<br />
value<br />
0 The STOP/RESET Key will function only when the Inverter is running with the run<br />
command through the Digital Operator.<br />
1 The STOP/RESET Key will be available anytime.<br />
Set the rated input current of the motor with n032 and the electronic thermal protective<br />
function with n033 to determine the motor protective characteristics.<br />
n032<br />
Motor Rated Current<br />
Setting range See note 1 Unit --- Default setting<br />
1<br />
Note<br />
Note<br />
Note<br />
1. The set value range is from 10% to 200% of the rated output current.<br />
2. The default-set value varies with the Inverter model.<br />
3. Be sure to set n032 after checking the rated input current of the motor.<br />
n033<br />
Electronic Thermal Protection Function Selection<br />
Setting range 0 to 4 Unit --- Default setting<br />
1<br />
Set Values<br />
Set<br />
Description<br />
value<br />
0 No protection.<br />
1 For standard motors with standard ratings (with a time constant of 8 min).<br />
2 For standard motors with short-time ratings (with a time constant of 5 min).<br />
3 For dedicated motors with standard ratings (with a time constant of 8 min).<br />
4 For dedicated motors with short-time ratings (with a time constant of 5 min).