OMRON Sysdrive 3G3HV - Detector Cooling Section
OMRON Sysdrive 3G3HV - Detector Cooling Section
OMRON Sysdrive 3G3HV - Detector Cooling Section
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Group 2: n035 to n049<br />
Function No. Name Description Setting<br />
range<br />
Sequential n035 Multi-function<br />
0: Reverse rotation/Stop<br />
0 to 24<br />
input function<br />
input 1 1: Stop command (3-wire sequence<br />
selection<br />
(S2)<br />
selection)<br />
S3 will be used for forward/reverse<br />
rotation command and value set with<br />
n036 will be ignored.<br />
2: External error (NO contact: ON)<br />
3: External error (NC contact: ON)<br />
4: Error reset (ON: Valid)<br />
5: Operation mode selection (ON: Digital<br />
Operator; OFF: n002)<br />
6: Not used<br />
7: Emergency stop<br />
8: Analog input selection (ON: Current<br />
input through FI terminal; OFF: FV<br />
terminal)<br />
9: Multi-step speed command 1<br />
10: Multi-step speed command 2<br />
11: Inching command<br />
12: Acceleration/Deceleration time<br />
switching command<br />
13: External baseblock command (ON:<br />
Valid)<br />
14: External baseblock command (OFF:<br />
Valid)<br />
15: Speed search command from max.<br />
frequency<br />
16: Speed search command from set frequency<br />
17: Parameter set-inhibit (ON: Invalid)<br />
18: Integral value of PID control reset<br />
command<br />
19: PID control invalidating command<br />
(Set point used as frequency reference)<br />
20: Timer function input (Set with n077<br />
and n078)<br />
21: Inverter overheat warning (ON: “OH3”<br />
will be displayed)<br />
22: Analog frequency sample hold<br />
23: Power OFF stop input (NO contact)<br />
24: Power OFF stop input (NC contact) [0]<br />
n036<br />
n037<br />
n038<br />
n039<br />
Multi-function<br />
input 2<br />
(S3)<br />
Multi-function<br />
input 3<br />
(S4)<br />
Multi-function<br />
input 4<br />
(S5)<br />
Multi-function<br />
input 5<br />
(S6)<br />
Same as n035 2 to 24<br />
[2]<br />
Same as n035 2 to 24<br />
[4]<br />
Same as n035 2 to 24<br />
[9]<br />
0to 22: Same as n035<br />
25: Up/Down command<br />
S5 will be used for the up command,<br />
S6 will be used for the down command,<br />
and value set with n038 will be<br />
ignored.<br />
2 to 25<br />
[10]<br />
User<br />
setting