• The functions of multi-function contact output 1 (MA, MB, and MC)<br />
and multi-function contact output 2 (M1 and M2) can be selected from<br />
the following.<br />
Set Values<br />
Set<br />
Description<br />
value<br />
0 Error (ON: Error)<br />
1 Running (ON: Running)<br />
2 Frequency agreement (ON: Frequency agreement)<br />
3 Optional frequency agreement (ON: Optional frequency agreement)<br />
4 Optional frequency detection (ON: Output frequency n073)<br />
5 Optional frequency detection (ON: Output frequency n073)<br />
6 Overtorque (ON: Detected)<br />
Set the detection method with n074, the detection level with n075, and the detection time<br />
with n076.<br />
7 Overtorque (OFF: Detected)<br />
Set the detection method with n074, the detection level with n075, and the detection time<br />
with n076.<br />
8 Baseblock (ON: Subject to the baseblock.)<br />
9 Operation mode (ON: Digital Operator/Frequency reference)<br />
10 Inverter ready (ON: Ready)<br />
Ready: The Inverter is turned ON and ready to operate normally.<br />
11 Timer function output (Set with n077 and n078)<br />
12 Error retrying (Valid if the error retry function is set with n056)<br />
13 Inverter/Motor overload warning (ON: Warning)<br />
Inverter overload warning: ON when the output of the Inverter is 150% of the rated<br />
output continuously for 48 s.<br />
Motor overload warning: ON when the motor is overloaded for a period as long as 80%<br />
of the motor overload protective time.<br />
14 Frequency reference loss (ON: Loss)<br />
Set n045 (i.e., analog frequency reference loss processing) to 1 (i.e., valid).<br />
Frequency reference loss is a phenomenon resulting in a value drop of a frequency<br />
reference by 90% or more within 0.4 s.<br />
If the Inverter detects frequency reference loss, the Inverter will continue running at a<br />
frequency 20% lower than the previous frequency.<br />
15 Not used<br />
16 PID feedback loss (ON: Loss)<br />
The Inverter will detect PID feedback loss if n092 (i.e., feedback loss selection) is set to<br />
1.<br />
Set the feedback loss detection level with n093 and the feedback loss detection time with<br />
n094.<br />
17 Heating heat sink (ON: OH1 will be detected)