• The functions of multi-function contact output 1 (MA, MB, and MC)<br />

and multi-function contact output 2 (M1 and M2) can be selected from<br />

the following.<br />

Set Values<br />

Set<br />

Description<br />

value<br />

0 Error (ON: Error)<br />

1 Running (ON: Running)<br />

2 Frequency agreement (ON: Frequency agreement)<br />

3 Optional frequency agreement (ON: Optional frequency agreement)<br />

4 Optional frequency detection (ON: Output frequency n073)<br />

5 Optional frequency detection (ON: Output frequency n073)<br />

6 Overtorque (ON: Detected)<br />

Set the detection method with n074, the detection level with n075, and the detection time<br />

with n076.<br />

7 Overtorque (OFF: Detected)<br />

Set the detection method with n074, the detection level with n075, and the detection time<br />

with n076.<br />

8 Baseblock (ON: Subject to the baseblock.)<br />

9 Operation mode (ON: Digital Operator/Frequency reference)<br />

10 Inverter ready (ON: Ready)<br />

Ready: The Inverter is turned ON and ready to operate normally.<br />

11 Timer function output (Set with n077 and n078)<br />

12 Error retrying (Valid if the error retry function is set with n056)<br />

13 Inverter/Motor overload warning (ON: Warning)<br />

Inverter overload warning: ON when the output of the Inverter is 150% of the rated<br />

output continuously for 48 s.<br />

Motor overload warning: ON when the motor is overloaded for a period as long as 80%<br />

of the motor overload protective time.<br />

14 Frequency reference loss (ON: Loss)<br />

Set n045 (i.e., analog frequency reference loss processing) to 1 (i.e., valid).<br />

Frequency reference loss is a phenomenon resulting in a value drop of a frequency<br />

reference by 90% or more within 0.4 s.<br />

If the Inverter detects frequency reference loss, the Inverter will continue running at a<br />

frequency 20% lower than the previous frequency.<br />

15 Not used<br />

16 PID feedback loss (ON: Loss)<br />

The Inverter will detect PID feedback loss if n092 (i.e., feedback loss selection) is set to<br />

1.<br />

Set the feedback loss detection level with n093 and the feedback loss detection time with<br />

n094.<br />

17 Heating heat sink (ON: OH1 will be detected)